Installation and User Manual
2.7
System Connections
WARNING
This type of connections must be carried out by qualified electrical personnel.
Before carrying out any connections, check that battery circuit breaker
is OFF and that the upstream protection devices (Normal and Bypass AC
sources) are open (OFF/OPEN).
2.7.1
Connections with Common Normal and Bypass AC Sources (Single Mains)
Figure 2-11: Power Module I/O Box Terminal Block Diagram.
NOTE
◗
The Power Module is factory configured for single input, whereas both Normal
AC and Bypass AC sources are identical, by means of jumper between L1 and L3.
◗
Jumper must be removed for separate Normal AC and Bypass AC sources
(2 Mains) or with Frequency Converter application.
◗
Keep Manual Bypass Switch
at Normal position.
7
L6 L5 L2 L1 L1 L4 L3
Jumper
(see note)
Output
200/208/220/230/240Vac
Normal AC source
200/208/220/230/240Vac
Bypass AC source
200/208/220/230/240Vac
Terminal block capacity:
- Max. 4AWG (EX 11RT)
- Max. 6AWG (EX 5/7RT)
14
Installation
2 — 13
86-86000-00 B01
Terminal tightening torque:
– 18 lb-in. for EX 5/7RT Power Module
– 35 lb-in. for EX 11RT Power Module
Summary of Contents for 11+
Page 1: ...w w w m g e o p s c o m EX 5 7 11 RT Systems Installation and User Manual ...
Page 2: ......
Page 4: ... This page left blank intentionally EX 5 7 11 RT Systems iv 86 86000 00 B01 ...
Page 14: ... This page left blank intentionally EX 5 7 11 RT Systems c x 86 86000 00 B01 ...
Page 46: ... This page left blank intentionally EX 5 7 11 RT Systems 2 20 86 86000 00 B01 ...
Page 62: ... This page left blank intentionally EX 5 7 11 RT Systems 4 6 86 86000 00 B01 ...
Page 68: ......
Page 72: ...EX 5 7 11 RT Systems G 4 86 86000 00 B01 This page left blank intentionally ...
Page 74: ......
Page 75: ......