4.3
Re-Connecting the Power Module
This operation can be performed without interrupting the load.
Figure 4-2: Reconnect the Power Module.
EX 5/7/11 RT Systems
Maintenance
4 — 4
86-86000-00 B01
1.
Secure the Input/Output box using the three
screws.
2.
Reconnect the cables
and
to the
Power Module.
3.
Switch the battery circuit breaker(s)
to the
ON position.
4.
Check if Normal AC source circuit breaker
is on the ON position.
5.
Check that the LED
is ON.
6.
Turn the manual bypass switch from the
BYPASS to the NORMAL position.
7.
Follow initial start up sequence (See Section 3.1)
in order to personalize the UPS.
8.
Push the ON button
for more than 3
seconds.
The green LED
is ON, and the connected
equipment is now protected by the UPS.
15
23
17
8
14
42
40
OFF
ON
17
LOAD LEVEL
4 kW/ 5 kVA
23
15