Installation and User Manual
4.4
Hot Swapping the Battery Module
During the replacement of the Battery Module, it is imperative to use the same type and number of element as the
original Battery Module provided with the UPS to maintain an identical level of performance and safety. In case of
doubt, please refer to our web site at www.mgeops.com or call (800) 279-7776.
Figure 4-3: Rear View of the Battery Module.
Maintenance
4 — 5
86-86000-00 B01
4.4.1
Disconnecting the Battery Module
1.
Switch the battery circuit breaker(s)
to the
OFF position.
2.
Disconnect the cables
and
from the
Power Module.
The Battery Module can be replaced.
The connected equipment is powered by the UPS,
but not protected.
It is also possible to replace the battery packs
instead of Battery Module.
CAUTION:
Always replace both
battery packs with
new ones.
To remove battery pack:
1.
First, switch the battery circuit breaker(s) to the
OFF position.
See Section 2.4.2 and follow instructions for battery
pack replacement.
4.4.2
Re-Connecting the Battery Module
1.
Reconnect the battery cables
and
to
the Power Module.
2.
Switch the battery circuit breaker(s)
to the
ON position.
14
42
40
42
40
14
42
40
14
Battery Module
Power Module
Summary of Contents for 11+
Page 1: ...w w w m g e o p s c o m EX 5 7 11 RT Systems Installation and User Manual ...
Page 2: ......
Page 4: ... This page left blank intentionally EX 5 7 11 RT Systems iv 86 86000 00 B01 ...
Page 14: ... This page left blank intentionally EX 5 7 11 RT Systems c x 86 86000 00 B01 ...
Page 46: ... This page left blank intentionally EX 5 7 11 RT Systems 2 20 86 86000 00 B01 ...
Page 62: ... This page left blank intentionally EX 5 7 11 RT Systems 4 6 86 86000 00 B01 ...
Page 68: ......
Page 72: ...EX 5 7 11 RT Systems G 4 86 86000 00 B01 This page left blank intentionally ...
Page 74: ......
Page 75: ......