3.0 Input/Output
Connections
Always connect the earth ground wire first!
3.1
Connect the three wires of the equipment cable to the “OUTPUT” terminal block.
3.2
Connect the three wires of the power cable to the “INPUT” terminal block.
L1 L2
L1 L2
INPUT OUTPUT
L1 L2 L3
INPUT
OUTPUT
120
104 N
104
120
208 VAC
FROM UTILITY
TO LOAD
208 VAC
I/O BOX
TO LOAD
120 VAC/208VAC/240VAC
OR
TO OPTIONAL POWER DISTRIBUTION MODULE (PDM)
- OR -
TO OPTIONAL
6 kVA ISO
TRANSFORMER
4.5/6 KVA CONFIGURATION
TERMINAL BLOCK LAYOUT
NOTE: UPS AND ISOLATION TRANSFORMER
ARE FACTORY CONFIGURED AT 208 VAC
Comet EXtreme Transformer Distribution Cabinet