2.2 Checking equipment compatibility

Check that the UPS and CLA modules are compatible:

UPS no.

Pulsar EX

treme

 CLA 2000

51033021

Pulsar EX

treme

 CLA 3000

51033031

CLA no.

51033029

51033539

2.3 Batteries to be used

Use only 12 V / 65 Ah lead-acid batteries.

Connect them as indicated below to obtain the required backup time:

2 hours

Pulsar EX

treme

 CLA 2000

1 string of 7
12V / 65Ah batteries

4 hours

8 hours

2. Installation

2 parallel-connected strings of 7
12V / 65Ah batteries

3 parallel-connected strings of 7
12V / 65Ah batteries

Backup time

This operation may be carried out only by qualified electricians using the necessary safety equipment for work on live parts
(insulated tools, gloves, goggles).

The connection of each module to the electrical supply must be protected by an easily accessible circuit
breaker (not supplied). A module can be isolated from the electrical supply by opening this circuit
breaker.

Before making any connections or working on the equipment, make sure the battery circuit breaker is in OFF
position and that the main contacts of the upstream protective devices of the electrical installation are open (OFF
position)

.

For maximum battery life, CLA and UPS modules must be installed in the same room as batteries so that the automatic
regulation of the charge voltage as a function of temperature can work correctly.

Pulsar EX

treme

 CLA 2000 Rack

51033521

51033529

Pulsar EX

treme

 CLA 3000 Rack

51033531

51033539

Pulsar EX

treme

 CLA 3000

1 string of 10
12V / 65Ah batteries

2 parallel-connected strings of 10
12V / 65Ah batteries

3 parallel-connected strings of 10
12V / 65Ah batteries

2.4 Connecting the batteries to the Pulsar EX

treme

 CLA module

Summary of Contents for 51033021

Page 1: ...MGE Pulsar EXtreme Pulsar EXtreme CLA 2000 3000 https eaton power ru catalog mge pulsar extreme...

Page 2: ...51033775EN AA Page 1 www mgeups com MGE UPS SYSTEMS Pulsar EXtreme CLA 2000 3000 VA Installation manual N O T H I N G W I L L S T O P Y O U N O W...

Page 3: ...Page 2 51033775EN AA...

Page 4: ...and checking the contents 1 Unpacking Pulsar EXtreme CLA 2000 3000 VA Tower model Rack model Pulsar EXtreme CLA module connection cable 1 2 documentation telescopic rails and 19 rack mounting hardwar...

Page 5: ...Page 4 51033775EN AA Mounting the rails in the rack The rails and the screws required to mount them are included in the box 2 1 Mounting Rack model 2 Installation 1 2 3 3 3 3 4...

Page 6: ...dule to the electrical supply must be protected by an easily accessible circuit breaker not supplied A module can be isolated from the electrical supply by opening this circuit breaker Before making a...

Page 7: ...ule 3 Mount the cable gland on the shielded cable 4 Connect the 3 conductors to the terminal block and refit the plate 5 Connect the other end of the cable to the circuit breaker 2 5 Connecting the Pu...

Page 8: ...the battery circuit breaker to ON position 2 Connect a PC to the UPS using an RS232 cable 3 Run the UPS Driver software installed on a diskette Go to the battery menu and select the battery backup ti...

Page 9: ...ower Pn 2 hr CLA 4 hr CLA 8 hr CLA 2 hrs 10 min 5 hrs 8 hrs 3 hrs 6 hrs 30 min 12 hrs 4 hrs 50 min 12 hrs 18 hrs Recharge time to 90 full backup time 2 hr CLA 6 hrs 4 hr CLA 8 hr CLA 12 hrs 21 hrs Ope...

Reviews: