Page 6 - 

51033775EN/AA

2. Installation

L +

BA
TTERIE/BA

TTER

Y

L -

4

2

25A

t

In

B

1

10

90

20

3

25A

12V-65Ah

5

Use a 3-conductor cable (shielded, max.
length 6 m, 3 x 4 mm

2

 conductors) to be

passed through the shielded cable gland.

Use a 25 A circuit breaker
(curve B) for protection.

Note: 

the cable and circuit breaker are not

supplied with the product.

1. Prepare the cable.

2. Unscrew the plate and dismantle the
metal cable gland on the 

Pulsar EX

treme

CLA

 module.

3. Mount the cable gland on the shielded
cable.

4. Connect the 3 conductors to the terminal
block and refit the plate.

5. Connect the other end of the cable to the
circuit breaker.

2.5 Connecting the Pulsar EX

treme

 CLA module to the power source

10

50

1

L +

RESEA

U/MAINS/NETZ

N

3

2

+

Use a flexible cable (3 x 2.5 mm

2

conductors) to be passed through the plastic
cable gland.

Always connect the earth wire
first. Use a 10 A circuit breaker
(curve C) for protection.

Note:

 the cable and circuit breaker are not

supplied with the product.

1. Prepare the cable.

2. Unscrew the plate with the plastic cable
gland.

3. Connect the 3 conductors and remount
the plate.

Summary of Contents for 51033021

Page 1: ...MGE Pulsar EXtreme Pulsar EXtreme CLA 2000 3000 https eaton power ru catalog mge pulsar extreme...

Page 2: ...51033775EN AA Page 1 www mgeups com MGE UPS SYSTEMS Pulsar EXtreme CLA 2000 3000 VA Installation manual N O T H I N G W I L L S T O P Y O U N O W...

Page 3: ...Page 2 51033775EN AA...

Page 4: ...and checking the contents 1 Unpacking Pulsar EXtreme CLA 2000 3000 VA Tower model Rack model Pulsar EXtreme CLA module connection cable 1 2 documentation telescopic rails and 19 rack mounting hardwar...

Page 5: ...Page 4 51033775EN AA Mounting the rails in the rack The rails and the screws required to mount them are included in the box 2 1 Mounting Rack model 2 Installation 1 2 3 3 3 3 4...

Page 6: ...dule to the electrical supply must be protected by an easily accessible circuit breaker not supplied A module can be isolated from the electrical supply by opening this circuit breaker Before making a...

Page 7: ...ule 3 Mount the cable gland on the shielded cable 4 Connect the 3 conductors to the terminal block and refit the plate 5 Connect the other end of the cable to the circuit breaker 2 5 Connecting the Pu...

Page 8: ...the battery circuit breaker to ON position 2 Connect a PC to the UPS using an RS232 cable 3 Run the UPS Driver software installed on a diskette Go to the battery menu and select the battery backup ti...

Page 9: ...ower Pn 2 hr CLA 4 hr CLA 8 hr CLA 2 hrs 10 min 5 hrs 8 hrs 3 hrs 6 hrs 30 min 12 hrs 4 hrs 50 min 12 hrs 18 hrs Recharge time to 90 full backup time 2 hr CLA 6 hrs 4 hr CLA 8 hr CLA 12 hrs 21 hrs Ope...

Reviews: