2. Installation

2.7 Connecting the UPS to the two Comet EX

treme

 CLA modules

Use the connection cables supplied with the
modules.

2.8 Setting the UPS

Before connecting the loads to be protected
and starting the system, the UPS must be
reconfigured using the UPS Driver software
supplied on a diskette with the UPS.

1. Switch the battery circuit breaker to ON
position.

2. Connect a PC to the UPS using an RS232
cable.

3. Run the UPS Driver software installed on
a diskette. Go to the "battery" menu and
select the battery backup time (2, 4 or 8
hours) corresponding to the new
configuration.

Once the backup time has been set, click to
save the settings and exit UPS Driver. This
procedure is necessary for fast recharge of
the batteries by the 

Comet EX

treme

 CLA

.

The installation is now ready and you can
connect the equipment to be protected.

50A

12V-65Ah

50A

1

ON

2

3

Summary of Contents for Comet EXtreme CLA 12 kVA

Page 1: ...51033777EN AB Page 1 www mgeups com MGE UPS SYSTEMS Comet EXtreme CLA 12 kVA Installation manual N O T H I N G W I L L S T O P Y O U N O W...

Page 2: ...Page 2 51033777EN AB...

Page 3: ...1 Unpacking Comet EXtreme CLA module connection cable documentation 1 2 connection box installation manual telescopic rails and 19 rack mounting hardware 4 5 Comet EXtreme CLA 12 kVA Tower model Rack...

Page 4: ...n the rack The rails and the screws required to mount them are included in the box To mount the connection box in a rack use the mounting brackets and screws packed with the connection box 2 1 Mountin...

Page 5: ...The connection of each module to the electrical supply must be protected by an easily accessible circuit breaker not supplied A module can be isolated from the electrical supply by opening this circui...

Page 6: ...ct the 3 conductors to the terminal block and refit the connection box cover 5 Connect the other end of the cable to the circuit breaker 2 6 Connecting the Comet EXtreme CLA modules to the power sourc...

Page 7: ...itch the battery circuit breaker to ON position 2 Connect a PC to the UPS using an RS232 cable 3 Run the UPS Driver software installed on a diskette Go to the battery menu and select the battery backu...

Page 8: ...r CLA 8 hr CLA 2 hrs 30 min 5 hrs 40 min 9 hrs 3 hrs 30 min 7 hrs 30 min 13 hrs 40 min 5 hrs 20 min 13 hrs 40 min 21 hrs Recharge time to 90 full backup time Comet EXtreme CLA 12kVA 2 hr CLA 9 hrs 4 h...