Comet installation and user manual: E-6761200XT/FC
2.1
Merlin Gerin by MGE UPS SYSTEMS
installation
(for qualified personnel only)
■
"Comet" cubicles are equipped with 4 wheels for moving over short distances
and with jacks to immobilize the unit. The jacks must be raised prior to
repositioning a cubicle;
■
operating temperature range: 0
°
to 30
°
C at rated output.
Important:
■
the battery is of the sealed type. Battery storage or prolonged shutdown
of Comet should never exceed 3 months at 20
°
C without recharging, for a
battery initially at 100% charge. Battery recharge requires system start-up.
The battery warranty is void if the 6 month recharge interval is not
respected;
■
battery life is extended when it is installed in a room with an ambient
temperature of 15 to 25
°
C. Above 25
°
C, battery life reduced by 50% for
every additional 10
°
C;
■
heat loss resulting from Comet operation must be taken into account when
sizing the ventilation system. See the Appendices;
■
connections are made through the bottom section in the back or the front,
depending on the type of Comet;
■
warning in compliance with EN 50091-2: this product is sold through limited
sales channels to installers or well-informed users. Installation restrictions or
additional measures may be necessary to prevent electromagnetic disturbances.
general
Fig. 8
"e" see note
100 mm minimum
(for ventilation)
air extraction
extended battery
option
other option
L1
L
P
P1
Comet
L2
L2
final positioning
(figure 8)
"Comet" layout seen from above