6000 UPS User’s Guide, Shared Systems (MGE part number 86-130034-00), and be familiar
with the indicators, controls, and operation of the UPS.
a.
Isolate and de-energize all EPS 6000 UPS equipment for
all maintenance operations.
b.
Ensure that all equipment is clean and free of loose dust, dirt, and debris. The
exterior of the enclosures may be cleaned with a mild solution of soap and water,
lightly applied with a lint-free cloth.
c.
Inspect the air intake and exhaust plates and clean as required. Verify that air flows
freely through the equipment. Clean the air intake and exhaust plates,
and the enclosure interior, with a vacuum cleaner.
d.
The EPS 6000 UPS module is equipped with air filters that should be changed at
regular intervals. Inspect the filters regularly to determine how long the filters will
last in your installation.
e.
Initiate the start-up procedure, as described in the User’s guide.
f.
Test the main operating sequences as applicable to your equipment configuration
and installation.
There are no user replaceable parts inside
the EPS 6000 UPS.
Three levels of replacement parts are available for the EPS 6000 UPS. The three levels are
designated A, B, and C. The level that you should keep on hand for your installation will vary
depending on the type of maintenance planned on site, and the configuration of your UPS
system. Having the replacement parts on hand will prevent any unacceptable delays (due to
time involved obtaining spare parts) during critical periods, such as system start-up.
Any items used during start-up will be replaced by MGE at no charge. Contact MGE Customer
Support Services for specific recommendations. A description of each level
is provided below:
Level
Description
A
This level of replacement parts consists of consumable items, specifically fuses
and air filters. It is recommended to have these items on hand during installation
of the UPS systems, including initial start-up.
B
This level of replacement parts is recommended when the user can tolerate
short-duration UPS down-time to obtain replacement parts in the event of a
major UPS failure. This level of replacement parts consists of consumable items,
specifically fuses, air filters, an inverter leg, and the most critical circuit board
assemblies.
C
This level of replacement parts is recommended when the user can tolerate only
a minimum of down-time in the event of a major UPS failure. This level of
replacement parts consists of consumable items, specifically fuses, air filters, an
inverter leg, and a complete set of circuit board assemblies.
4.3
Replacement Parts
4 — 2
Maintenance
EPS 6000 Uninterruptible Power System
Summary of Contents for EPS 6000
Page 1: ...EPS 6000 UPS Uninterruptible Power Systems Installation Manual...
Page 10: ...this page left blank intentionally EPS 6000 Uninterruptible Power System...
Page 40: ...this page left blank intentionally EPS 6000 Uninterruptible Power System...
Page 50: ...this page left blank intentionally EPS 6000 Uninterruptible Power System...
Page 70: ......
Page 71: ......