background image

Quick Start

3

86-86000-03 B00

STEP 4    Systems Connections

EX RT Transformer Module Quick Start

EX RT Transformer Module, Power Module, and Battery Module Connections

System Connections with Transformer Module

AC Normal  INPUT

Transformer   OUTPUT TO LOAD

Battery Module 
EXB 5/7/11RT

Power Module
EX 5/7/11 RT

Transformer 
Module EX RT

Transformer 
Main Output
Circuit Breaker

Follow connection 
diagram for appropriate 
input/output voltages.

Connection Diagram
(bottom of Transformer I/O Box)

L3              L2                L1             Lb            Ld        N          Lc         La

208Vac

240Vac

AC Input

120Vac

208Vac

AC Output

120Vac

240Vac

Transformer Module Terminal block capacity: 
maximum 4 AWG  solid or stranded wire on 
transformer module.

1.   Check that the battery circuit breaker  is OFF (“0”) position.

2.   Connect the battery power cable  to the connectors of the power and battery modules,

3.   Connect the battery detection cable  between connectors  of the power and battery modules.

4.   Turn on battery module circuit breaker, power module, I/O Box, circuit breaker, and Transformer Module
      Main Output Circuit Breaker.

5.  Push ON button on the Power Module for more than 3 seconds.

Battery Module

Circuit Breaker

Battery  Power 

Cable

Power Module

Connector

Battery  Detection 

Cable

1

2

3

Power Module Circuit Breaker

4

4

See EX 5/7/11RT Systems Installation and User Manual for initial start-up procedures. 

Summary of Contents for EX 5RT

Page 1: ...s c o m EX RT Transformer Module Quick Start Standard Features When used with standard system EX RT Transformer Module provides isolated and Step down 120 208 240 Vac outputs Multiple Output receptacles 120 208 240 Vac ...

Page 2: ......

Page 3: ...er Quick Start Manual EX RT Transformer Module Box Contents Tower Stand Extenders Stabilizer Bracket 4 screws included 41 Transformer Rail Kit Transformer Cable w w w m g e o p s c o m EX 5 7 11RT Systems Quick Start Tower Configuration of Standard System with Transformer Module Transformer Module E X 11 R T E X B 11 R T Power Module Battery Module up to 6 Power Module Battery Module Transformer M...

Page 4: ...r 3 BATTERY MODULE lower EXB 5 7 11 RT 4 BATTERY MODULE bottom EXB 5 7 11 RT Shown with power module and 2 battery modules B Rack Installation 3 4 4 4 4 2 2 1 4 4 5 1 6 6 6 1 Attach both front mounting ear brackets to module with supplied screws For this step it is possible to adjust the position of both front mounting brackets 2 Attach rear support brackets to module These brackets prevent the mo...

Page 5: ...ac 240Vac Transformer Module Terminal block capacity maximum 4 AWG solid or stranded wire on transformer module 1 Check that the battery circuit breaker is OFF 0 position 2 Connect the battery power cable to the connectors of the power and battery modules 3 Connect the battery detection cable between connectors of the power and battery modules 4 Turn on battery module circuit breaker power module ...

Page 6: ......

Page 7: ......

Page 8: ...te 101 Irvine California 92618 www mgeops com w w w m g e o p s c o m Contact MGE Office Protection Systems United States MGE Office Protection Systems 13 Whatney Suite 101 Irvine CA 92618 949 268 2800 www mgeops com ...

Reviews: