www.mgeups.com
T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
Network Management Cards – User Manual
34003676EN/AA
Page 35/42
5.1.2 Choice 2: UPS parameters
The blue lines are those displayed on screen.
+============================================================================
+
| [ UPS Parameters Menu ] |
+============================================================================
+
SNMP/Web Agent Version : CAb8 (SN 49DC40116)
Ethernet address : 00 E0 D8 09 85 78
Agent BIOS Version : AB
1. Log Periodicity : 60
Value between 20 and 99999. Enables initialisation of the save frequency of Measurements, Events
and System in the Log menu. Default value = 60 sec.
2. Trap Port Number : 162
Numeric field limited to 65534. Enables forwarding of the traps sent by the card to a port other than the
one usually used for SNMP. Default value 162
3. System Date (yyyy/mm/dd) : 2003/06/10
Enables adjustment of the date
4. System Time (hh:mm:ss) : 14:47:53
Enables adjustment of the time
0. Return to previous menu
5.1.3 Choice 3: Access control
+============================================================================
+
| IP Address Community String Access |
+============================================================================
+
[1] 0.0.0.0 public NotAccess
[2] 0.0.0.0 public NotAccess
[3] 0.0.0.0 public NotAccess
[4] 0.0.0.0 public NotAccess
COMMANDS -
1. Modify - Modify an entry of table
2. Reset - Reset an entry to default from table
0. Return to previous menu
Please Enter Your Choice =>
This menu enables configuration of access to the four supervision stations (identified by the IP
address) with read/write community names different to those already defined in the card “1” menu.
First enter the figure corresponding to the command to be carried out, then the number of the target
input.
The example below shows how to configure the read/write rights for a station (172.17.1.1) with a
community name
MyCom: