6.  Performance & Product Specifications 

120V model 

NOVA 600 AVR 

NOVA 1100 AVR 

UPS power rating --- VA 

600VA 

1100VA 

UPS power rating --- W 

360W 

660W 

Input mains voltage range 

89-151V±5% 

89-151V±5% 

Output voltage in mains mode 

102-132V±5% 

102-132V±5% 

Output voltage in bat mode  

120V + 10/-15%  (102-132V) 

120V + 10/-15%  (102-132V) 

Output frequency in bat mode 50/60Hz±1Hz 

50/60Hz±1Hz 

Deep discharge protection 

4 hours 

4 hours 

UPS backup time 

15 minutes for 1 sets PC 

15 minutes for 2 sets PC 

UPS output waveform 

Quasi-sine 

Quasi-sine 

Input/Output cord 

NEMA 15A 

NEMA 15A 

Input protection 

Circuit breaker 10A/250V Circuit 

breaker 

20A/250V 

Recharge time 

8 hours to recover 80% after 

complete discharge 

8 hours to recover 80% after 

complete discharge 

Battery 

Sealed lead acid battery 

12V/7.2Ah x 1 

Sealed lead acid battery 

12V/7.2Ah x 2 

Surge rating (joule) 

175J 

175J 

Operating temperature 

0-40

°C

 0-40

°C

 

Relative humidity 

10-90% 

10-90% 

Product size (D x W x H) 

13.8 * 4.9 * 5.6 inch 

14.8 * 6.7 * 7.4 inch 

Product weight 

15 Lbs 

27 Lbs 

 
 

7. Trouble Shooting  

Condition 

Item need to check 

LED (green) is off, UPS has no output 

Check if the UPS is correctly plugged to the AC 
power available and UPS is turned “ON” 

 

UPS has little or no backup time 

Charge UPS during 8 hours and try again. Consider 
to replace battery if backup time is short. 

 Red ON and beep keep alarm 

Potential internal failure. Restart UPS. If red LED 
still light, call for assistance. 

 Red Blinking and 1 beep every 0.5 second 

UPS lightly or heavily overload, reduce load. Reset 
circuit breaker or change fuse on UPS if necessary 

 Red ON 

Faulty battery. Recharge battery. Replace battery if 
fault reappears. 

 

Any information or advice, please visit our web sit at 

www.mgeups.com

 or contact MGE UPS SYSTEMS 

after-sales service. 
 
 

8.  DB-9 cable wiring for serial model 

 

MGE UPS SYSTEMS           NOVA AVR User’s Manual / MAU-00026 AA                                Page 6 

Summary of Contents for Nova 1100 AVR

Page 1: ...Ma an nu ua al l M Ma an nu ue el l d d i in ns st ta al ll la at ti io on n e et t d d u ut ti il li is sa at ti io on n N No ov va a 6 60 00 0 A AV VR R N No ov va a 1 11 10 00 0 A AV VR R B Ba at t...

Page 2: ...ily accessible The UPS can be disconnected from the AC power source by removing the power cord Check that the indications on the rating plate correspond to your AC power system and to the actual elect...

Page 3: ...cessories NOVA1100 AVR NOVA 600 AVR USB Cable Installation and User Manual 3 or 4 NEMA 5 15R receptacles for peripherals to UPS Computer Monitor And Modem Input LIne Core NEMA 5 15P NOTE Management so...

Page 4: ...indicated time remaining is an approximation based on several load power curves 2 If the utility power failure exceeds the battery backup time the UPS will shut down to prevent excessive battery disch...

Page 5: ...ilar to NOVA 600 AVR except the 1100 VA has two 2 batteries Total battery voltage is 12V for NOVA 600 AVR and 24V for NOVA 1100 AVR Disposal of the old battery Never throw the battery in a fire risk o...

Page 6: ...rating joule 175J 175J Operating temperature 0 40 C 0 40 C Relative humidity 10 90 10 90 Product size D x W x H 13 8 4 9 5 6 inch 14 8 6 7 7 4 inch Product weight 15 Lbs 27 Lbs 7 Trouble Shooting Cond...

Page 7: ...r seau lectrique s effectue en d branchant le cordon d alimentation V rifier les indications port es sur la plaque d identification elles doivent correspondrent votre r seau lectrique d alimentation e...

Page 8: ...VA AVR et ses accessoires NOVA1100 AVR NOVA 600 AVR USB Cable Installation and User Manual 3 or 4 NEMA 5 15R receptacles for peripherals to UPS Computer Monitor And Modem Input LIne Core NEMA 5 15P NO...

Page 9: ...Bip continu D faut interne Rouge clignotant 1 bip toutes les 0 5 seconde Surcharge Rouge Aucune D faut batterie Nota 1 D s que l ASI est aliment e la batterie se charge quelle que soit la position du...

Page 10: ...A 600 AVR avec 2 batteries l int rieur La tension batterie est de 12V pour NOVA 600 AVR et 24V pour NOVA 1100 AVR Mise au rebut des batteries Ne pas jeter la batterie au feu risque d explosion Ne pas...

Page 11: ...t 0 40 C 0 40 C Humidit 10 90 10 90 Dimensions 13 8 4 9 5 6 inch 14 8 6 7 7 4 inch Poids 15 Lbs 27 Lbs 7 D pannage Sympt me Rem de Le bouton vert est teint et il n y a pas de tension en sortie de l AS...

Page 12: ...MGE UPS SYSTEMS NOVA AVR User s Manual MAU 00026 AA Page 12...

Page 13: ...geups com www mgeups com Canada MGE UPS SYSTEMS 9 2789 Thamesgate Drive Mississauga ONL4T 4E8 Tel 905 672 0990 877 672 0990 Fax 905 672 7667 email info mgeups com www mgeups com Latin America and Othe...

Reviews: