6. Performance & Product Specifications
120V model
NOVA 600 AVR
NOVA 1100 AVR
UPS power rating --- VA
600VA
1100VA
UPS power rating --- W
360W
660W
Input mains voltage range
89-151V±5%
89-151V±5%
Output voltage in mains mode
102-132V±5%
102-132V±5%
Output voltage in bat mode
120V + 10/-15% (102-132V)
120V + 10/-15% (102-132V)
Output frequency in bat mode 50/60Hz±1Hz
50/60Hz±1Hz
Deep discharge protection
4 hours
4 hours
UPS backup time
15 minutes for 1 sets PC
15 minutes for 2 sets PC
UPS output waveform
Quasi-sine
Quasi-sine
Input/Output cord
NEMA 15A
NEMA 15A
Input protection
Circuit breaker 10A/250V Circuit
breaker
20A/250V
Recharge time
8 hours to recover 80% after
complete discharge
8 hours to recover 80% after
complete discharge
Battery
Sealed lead acid battery
12V/7.2Ah x 1
Sealed lead acid battery
12V/7.2Ah x 2
Surge rating (joule)
175J
175J
Operating temperature
0-40
°C
0-40
°C
Relative humidity
10-90%
10-90%
Product size (D x W x H)
13.8 * 4.9 * 5.6 inch
14.8 * 6.7 * 7.4 inch
Product weight
15 Lbs
27 Lbs
7. Trouble Shooting
Condition
Item need to check
LED (green) is off, UPS has no output
Check if the UPS is correctly plugged to the AC
power available and UPS is turned “ON”
UPS has little or no backup time
Charge UPS during 8 hours and try again. Consider
to replace battery if backup time is short.
Red ON and beep keep alarm
Potential internal failure. Restart UPS. If red LED
still light, call for assistance.
Red Blinking and 1 beep every 0.5 second
UPS lightly or heavily overload, reduce load. Reset
circuit breaker or change fuse on UPS if necessary
Red ON
Faulty battery. Recharge battery. Replace battery if
fault reappears.
Any information or advice, please visit our web sit at
www.mgeups.com
or contact MGE UPS SYSTEMS
after-sales service.
8. DB-9 cable wiring for serial model
MGE UPS SYSTEMS NOVA AVR User’s Manual / MAU-00026 AA Page 6