MGE UPS SYSTEMS

Pulsar EX

Rack : 86-153500-00

i

IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE  INSTRUCTIONS

This manual contains important instructions for Models EX20Rack / EX30Rack / EXB20/30 that should be
followed during installation and maintenance of the UPS batteries.

c

This equipment can be operated by any

individual, with no previous training;

c

CAUTION: Risk of electric shock, even

with unit disconnected from AC power
source. Hazardous voltage still may be
present through operation from battery.
The battery supply should be disconnected
at the plus and minus terminals using the
quick disconnect connectors of the battery
when maintenance or service work inside
the UPS is necessary.

c

The UPS contains voltages which are

potentially hazardous. All repairs should
be performed by qualified service
personnel only;

c

do not attempt to power the UPS from

any receptacle other than a 2-pole 3-wire
grounded receptacle;

c

do not place Pulsar near water or in

environment of excessive humidity;

c

do not allow liquids or any foreign objects

to get inside Pulsar;

c

do not block air vents in front or back of

Pulsar;

c

do not plug household appliances such as

hair dryers to Pulsar receptacles;

c

do not place Pulsar in direct sunlight or

close to a heat-emitting source;

c

CAUTION: do not dispose of battery or

batteries in a fire. The battery may explode;

c

CAUTION: do not open or mutilate the

battery or batteries, released electrolyte is
harmful to the skin and eyes. It may be toxic;

c

CAUTION: a battery can present a risk of

electric shock and high short circuit current.
The following precautions should be
observed when working with batteries:

v

remove watches, rings or other metal

objects,

v

use tools with insulated handles,

v

wear rubber gloves, boots and safety

glasses;

c

please dispose of the packaging in

accordance with applicable laws.

c

the AC power receptacle should be near

the equipment and easily accessible. To
isolate Pulsar from AC input, remove the
input power cord from the AC power
receptacle;

c

if Pulsar is to be stored for a long time, it

is recommended to recharge the batteries
(by connecting AC power source to Pulsar,
switch "ON" or "OFF"), once a month for 24
hours to avoid a full battery discharge;

c

Pulsar contains batteries that should be

disposed of or recycled in accordance with
local applicable laws;

c

prior to installation, store Pulsar in a dry

location;

c

storage temperatures must be between

–4

°

F (-20

°

C) and  +113

°

F (+45

°

C);

c

servicing of batteries should be performed

or supervised by personnel knowledgeable
of batteries and the required precautions.
Keep unauthorized personnel away from
batteries;

c

when replacing the batteries, use the

same number and the following type of
batteries:

v

Pulsar EX20

Rack: 8 x 12V - 7.2Ah,

v

Pulsar EX30

Rack: 8 x 12V - 7.2Ah;

c

~

 : alternating current supply symbol;

Summary of Contents for Pulsar EX20Rack

Page 1: ...User Manual PulsarTM EX20Rack EX30Rack www mgeups com ...

Page 2: ...t Note this equipment has been tested and found to comply with Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when equipment is operated in a residential environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interfere...

Page 3: ...or batteries in a fire The battery may explode c CAUTION do not open or mutilate the battery or batteries released electrolyte is harmful to the skin and eyes It may be toxic c CAUTION a battery can present a risk of electric shock and high short circuit current The following precautions should be observed when working with batteries v remove watches rings or other metal objects v use tools with i...

Page 4: ...puter systems range from data losses to hardware damage power supplies hard disks Pulsar EX20Rack and EX30Rack are specially designed to protect network servers and all other interconnection devices that are sensitive to electrical disturbances Pulsar EX20Rack and EX30Rack add fault tolerance to the utility supplying your sensitive equipment Pulsar EX20Rack and EX30Rack are designed as compact uni...

Page 5: ...ault intrusion etc c battery extension module Pulsar EXB20 30 battery extension modules lengthen the battery time of the Pulsar EX20Rack EX30Rack to meet your requirements For rack installation of EXB20 30 order 19 rack kit P N 8907U c output transformer input line cord plugs into the Pulsar EX30Rack output receptacle Rating is 120V AC input 208V 240V AC 2 75 kVA output c maintenance bypass switch...

Page 6: ...automate system shutdown supervise and remotely control the UPSs MGE UPS SYSTEMS created Solution PacTM for this purpose Solution PacTM combines all these functions in a single CD ROM usable in local or remote mode TCP IP and SNMP and covering the main network environments Solution PacTM is the ideal solution for protecting networks and multiserver systems Solution PacTM on a single CD ROM contain...

Page 7: ...ulsar EX20Rack EX30Rack EXB20 30 presentation general contents Pulsar presentation 3 getting started operation 11 Pulsar EXRack 86 153500 00 MGE UPS SYSTEMS 1 2 Pulsar EXRack 86 153500 00 MGE UPS SYSTEMS ...

Page 8: ...lsar EXRack 86 153500 00 7b 5 7a 9 12 11 10 7c 6 13 8 7a Pulsar EXRack 86 153500 00 3 MGE UPS SYSTEMS 4 MGE UPS SYSTEMS Pulsar EX20Rack EX30Rack front view Pulsar EX20Rack rear view 1d 1b 1c 1f 1e 1a 2 3 ...

Page 9: ...MGE UPS SYSTEMS Pulsar EXRack 86 153500 00 5 Pulsar EX30Rack rear view 9 8 12 11 10 7c 7b 5 6 13 7a ...

Page 10: ... page iii rear view 18 CIRCUIT BREAKER 120Vdc 40A 19 23 Volt 96Vdc 20A Volt 96Vdc 20A 22 20 21 MGE UPS SYSTEMS ATTN CUSTOMER SUPPORT SERVICES 1660 SCENIC AVENUE COSTA MESA CA 92626 PLACE STAMP HERE 14 17 The indispensable companion sofware for your UPS L indispensable complément logiciel de votre onduleur solution pac 98 ...

Page 11: ...d operating on bypass fault tolerant mode yellow indicator LEDs 1a to 1d continuously or flashing slowly indicate the battery charge level if utility power present or remaining battery time if no utility power present They may be on continuously or flash slowly during a transition period By pressing the button marked function 2 when utility power is present they indicate the load charge level 1e g...

Page 12: ... life 4 or 5 years is halved every 10 C above 25 C c output specifications v voltage V single phase 120V 3 can be adjusted from 100 to 127V using EX Driver v frequency F 50 60Hz 0 5 frequency configuration using EX Driver c environment v noise level 50dBA for operation on utility power 50dBA for battery backup mode v operating temperature 0 to 35 C v relative humidity 0 to 90 non condensing c dime...

Page 13: ...30Rack battery back up time 3000VA 1500VA 750VA t hours Pulsar EX30Rackalone Pulsar EX30Rack 1 Pulsar EXB20 30 Pulsar EX30Rack 2 Pulsar EXB20 30 0 1 2 3 4 5 2000VA 1500VA 1000VA 500VA t hours Pulsar EX20Rack alone Pulsar EX20Rack 1 Pulsar EXB20 30 Pulsar EX20Rack 2 Pulsar EXB20 30 0 1 2 3 4 5 ...

Page 14: ...10 Pulsar EXRack 86 153500 00 MGE UPS SYSTEMS ...

Page 15: ... contents getting started 12 location 12 preliminary checks 12 connections 12 communication 13 operation 14 starting up with utility power present 14 starting up with out utility power 15 operation on battery 16 overload 17 operating anomalies 17 ...

Page 16: ...lsar EX20Rack EX30Rack v if the installation has 2 battery modules connect the second cord to the DC connector of the second module and to the first module v the use of connectors is strictly limited to connecting the battery modules to the Pulsar EX20Rack EX30Rack Any other connection to these connectors is prohibited and risks damaging the battery not covered by warranty v to start flip the batt...

Page 17: ...supplied to COM1 to COM4 set up by EX Tuner serial port of your computer equipped with Windows 3 1 or 95 98 on the one end and to the serial Pulsar EXRack connector on the other end Insert the CD and type A Install Follow the installation instructions on the screen 11 5 4 3 2 1 9 8 7 6 0V RD TD standard port 12 5 4 3 2 1 9 8 7 6 0V 0V n o n c 0V n o 0V n o 0V n o Relay breaking capacity Vmax 25V D...

Page 18: ... UPS is on utility power 1 s beep output off output off normal operation indicator lights test press button on off automatic sequence your load is supported by the battery device and battery test indicating the remaining battery time percentage here 50 indicating the recharge percentage of the battery here 50 silence silence ...

Page 19: ...t off output off normal operation on battery indicator lights test press on off button automatic sequence your load is supported by the battery UPS is on utility power device and battery test indicating the remaining battery time percentage here 50 1 beep every 10 s 3 s beep indicating the remaining autonomy percentage here 50 ...

Page 20: ...on button allows you to force a transfer on bypass push three times within 5 seconds and to come back on normal operation push again three times within 5 seconds If utility power is present hold alarm silence button in x ε mn x mn 0 mn Pulsar switches off automatically warning alarm at low battery indicating the remaining battery time here between 75 and 87 silence 1 beep every 10 s your load is s...

Page 21: ...d the following occurs recharge your battery for 8 hours operation on bypass see overload and device fault section Note This operating mode provides temporary inverter fault tolerance no utility power present Pulsar switches off automatically after a length of time which depends on the level of overload Note overload occurs if the load consumption is greater than the rated power of Pulsar To ackno...

Page 22: ...18 Pulsar EXRack 86 153500 00 MGE UPS SYSTEMS ...

Page 23: ...anies and are referred to in an editorial fashion only two years warranty policy c MGE UPS SYSTEMS Inc herein after referred to as MGE warrants Pulsar equipment manufactured by MGE to be free from defects in materials and workmanship for a period of two years from date of purchase If within such period purchaser discovers defective item and promptly notifies MGE in writing MGE shall repair or repl...

Page 24: ...Postal address 1660 Scenic Avenue Costa Mesa CA 92626 714 557 1636 MGE UPS SYSTEMS Inc www mgeups com 86 153500 00 ...

Reviews: