Page 26 -
51033211EN/AC
4. Maintenance
Indication
LED flashes and the buzzer
beeps.
LED flashes.
Signification
UPS
electronics have detected a
UPS
fault.
Depending on the
UPS
personalization
parameters (see section 3.5), there are
two possibilities:
◗
the equipment connected to the
UPS
continues to be supplied, but directly
from the AC-power source (via the
automatic bypass for a maximum of 8
hours (LED ON);
◗
the connected equipment is no longer
supplied.
The equipment connected to
the
UPS
is no longer protected.
A battery fault was detected during the
battery test.
Correction
For
UPS
s equipped with Hot
swap or Install connection
modules, follow the
UPS
replacement procedure (see
section 4.2).
Call the after-sales support
department.
Call the after-sales support
department because the
batteries need replacing.
15
16
Troubleshooting requiring MGE after-sales support
21
Summary of Contents for Pulsar EXtreme2000
Page 34: ...Page 34 51033211EN AC...