2. Installation
2.9 Extended battery (EXB) connections
2.10 Connection of IEC cables to output receptacles
This type of connection must be carried out by qualified electrical personnel
It is not necessary to shutdown the UPS in order to install the extended battery (EXB) module.
Up to three batteries may be connected to each levels of the Pulsar MX Frame.
The sequence below shows connection for two battery cabinets per level on a Pulsar MX Frame 20000 RT model.
1 - Check that the battery circuit breaker
(1)
of
each EXB is OFF ("0" position).
Start the following operations from the
lowest level:
2 - Connect the battery cable
(2)
to the UPS
battery power connector
(3)
and the other
end of the battery cable to the EXB battery
power connector
(4)
.
3 - Connect the battery detection cable
(5)
to
the UPS battery detection connector
(6)
and
the other end of the battery detection cable to
the EXB battery detection connector
(7)
.
4 - Connect the inter-EXB battery cable
(8)
to
the second EXB battery power connector
(9)
and the other end of the battery cable to the
second EXB battery power connector
(10)
of
the above EXB.
5 - Connect the battery detection cable to the
second EXB battery detection connector
(11)
and the other end of the battery detection
cable to the second EXB battery detection
connector
(12)
of the above EXB.
6 - Repeat operations 2 to 5 to other levels
7 - Close the battery circuit breaker
(1)
of
each EXB ("I" position).
Caution: a battery can cause electrocution and high short circuit currents.
Do not dispose of batteries in a fire. The battery may explode
Do no open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
1 - Connect the equipments to the UPS using
the cables
(1)
.
It is preferable to connect the priority
equipments to the two outlets
(3)
and the non
priority equipments to the two outlets
(2)
that
can be programmed in pairs.
Connect any high-power devices to the 16 A
outlet
(4)
To program shutdown of outlets
(2)
during
operation on battery power and thus optimise
the available backup time, the MGE UPS
SYSTEMS communication software is
required.
2 - Fit the connection securing system
(5)
that
prevents the plugs from being pulled out
accidentally.
2 6
7
4
5
11
10 9
8
1
3
12
3
1
4
2
5