3.3
Transfer Operations
3.3.1
Automatic Transfers
Automatic transfer of the load from one source to the other is accomplished by turning off the
active
source SCR's
and turning on the
inactive
source SCR's in a sequence and timing that allows a combined sense and on transfer
time of less than one quarter cycle (4.17ms). Automatic transfer is initiated under any of the following conditions,
provided transfer is authorized and the “inactive” source is not more degraded than the “active” source:
a)
Under-voltage on any phase of the
active
source.
b)
Over-voltage on any phase of the
active
source.
c)
Under-frequency of the
active
source.
d)
Over-frequency of the
active
source.
e)
Open SCR on the
active
source (transfer to
inactive
source, then shunt trip the
active
C.B. and inhibit
retransfer until repair is made and the system is reset).
f)
Shorted SCR on the
inactive
source (transfer to shorted
inactive
source, then shunt trip the previously
active
C.B. to prevent retransfer. Inhibit transfers and retransfers until repair is made and the system is reset).
g)
SCR Over-temperature on the
active
source (if there are no current overload faults, transfer to
inactive
source
and inhibit re-transfer until repair is made and the system is reset. If
inactive
source subsequently fails, transfer
back to the
active
side if it is within acceptable limits, including over-temperature limits).
h)
SCR Gate Drive power supply failure on the
active
source (transfer to
inactive
source and inhibit re-transfer
until repair is made and the system is reset).
i)
TVSS failure on the
active
source (if optional TVSS is installed).
3.3.2
Manual Transfers
The STS can be operated as a manual switch when the
Manual Control
keyed switch on the front panel is in the
ON position, enabling the manual control pushbuttons and some setpoint changes, for the following manual opera-
tions:
a)
Manual
Change Preferred Source
Pushbutton – Selects other source as Preferred, causing a transfer (without
break) to the selected source if it is available and within acceptable limits and is not the active source. If the
two sources are outside the preset
in sync
phase window, a transfer (with break) can be made by pressing the
manual
Override Limits
pushbutton simultaneously.
b)
Manual
Return to Preferred Source
Pushbutton - If auto-retransfer is disabled, pressing this pushbutton will
initiate a retransfer back to the preferred source, overriding owner selected auto retransfer time delay.
To prevent normal automatic transfers, the operator can use the
Change Preferred Source
pushbutton to transfer
to the desired source, and then shut down the feeder to the other inactive source.
3.3.3
Automatic Retransfers
Automatic retransfer of the load from the alternate source back to the preferred is accomplished by turning off the
active
alternate source SCR's and turning on the
inactive
preferred source SCR's in a sequence and timing that
allows a combined sense and transfer time of less than one quarter cycle (4.17ms). Providing the
inactive
preferred
source is not more degraded than the
active
alternate source, retransfer will occur under the following conditions:
a)
If retransfer is not prohibited, retransfer will occur after an owner selected time delay after the preferred source
becomes available and within acceptable limits.
b)
If retransfer is prohibited, retransfer can be manually initiated by pressing the manual
Return to Preferred
Source
Pushbutton (Pre-conditions:
Manual Control
switch in ON position;
inactive
preferred source is
available and within acceptable limits). Transfer is temporarily authorized for a preset time.
Epilson STS
TM
Operation
3 —4
86-504004-00 B03
Summary of Contents for STS 400A
Page 2: ......
Page 28: ... This page left blank intentionally Epilson STSTM 1 12 86 504004 00 B02 ...
Page 54: ... This page left blank intentionally Product Name 3 16 86 504004 00 B02 ...
Page 58: ... This page left blank intentionally Product Name W 4 86 504004 00 B02 ...
Page 62: ... This page left blank intentionally Epilson STSTM G 4 86 504004 00 B03 ...
Page 64: ......
Page 65: ......