Flow temp setpoint
room stat
---/P1340 - ---/P1341
---
°C
1344
Swi-on ratio room stat
---/1
– 99
---
%
1346
Delay Heat request
0
– 600
0
S
1350
Room Influence
---/1
– 100
---
%
1360
Room temp limitation
---/0.5
– 4
1
°C
1361
Heating limit room
controller
---/0
– 100
---
%
1370
Boost heating
---/0
– 20
5
°C
1380
Quick setback
Off, Down to Reduced Setpoint,
Down to Frost Protection Setpoint
To Reduced
Setpoint
-
1390
Optimum start control
max
0
– 360
0
Min.
1391
Optimum stop control
max
0
– 360
0
Min.
1394
Heat up gradient
0
– 600
60
Min/k
1400
Reduced setp.
increase start
---/P1401
– 10
---
°C
4101
Reduced setp.
increase end
-30
– P1400
-15
°C
1409
Continuous pump
operation
No
– Yes
No
1412
Frost protection flow
temp.
Off
– On
On
1420
Overtempprot. pump
circuit
Off
– On
On
-
1430
Mixing valve boost
0
– 50
5
°C
1432
Actuator type
Two Position
– Three Position
Three-position
-
1433
Switching differential
2-pos
0
– 20
2
°C
1434
Actuator running time
30
– 873
120
S
1435
Mixing valve Xp
1
– 100
32
°C
1436
Mixing valve Tn
10
– 873
120
S
1450
Floor curing Function
Off, Function heating, Curing heating,
Fu Curing heating,
functional heating, Manually
Off
-
1451
Floor curing setp.
manually
0
– 95
25
°C
1455
Floor curing setp.
current
0
– 95
°C
1456
Floor curing day
current
0
– 32
1461
Excess heat draw
Off, Heating mode, Always
Always
1470
With buffer
No, Yes
Yes
-
1472
With prim
contr./system pump
No, Yes
Yes
1480
Pump speed reduction
According HC operating level,
According characteristic curve,
Temp. differential nominal
According
characteristic
curve
1481
Starting speed
0
– 100
100
%
1482
Pump speed min
P1485
– P1483
50
%