© MHG Heating Ltd
37
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR
Telephone 08456 448802 Fax 08456 448803 Email
info@mhgheating.co.uk
Web www.mhgheating.co.uk
140116
2476
Flue gas superv.
Shutdown
Start pre-ventilation, Lockout position
Lockout position
2477
Flue gas superv. st.
prev. time
10
– 218
10
Min.
2478
Flue gas temp output
limit
0
– 200
80
°C
2479
Fl’gsuperv. time con
rel mod
0
– 50
0
S
2480
Static press superv.
sh’down
Start preventilation, Lockout position
Lockout position
2490
Dyn press superv.
sh’down
Start preventilation, Lockout position
Lockout position
2491
Dynsuperv. press diff
min
0
– 5
0
Bar
2492
Dynsuperv. press diff
max
0
– 5
5
Bar
2494
Dynsuperv. press
increase
No, Yes
Yes
2495
Dyn press superv time
0
– 10
0.2
S
2630
Auto deaeration
procedure
Off, On
Off
Cascade
3510
Lead Strategy
[Late on, Early off], [Late on, late off],
[Early on, late off]
Late on, Late off
3511
Output ban min
0
– P3512
40
%
3512
Output ban max
P3511
– 100
90
%
3530
Release integral
source seq.
0
– 500
50
°C*min
.
3531
Reset integral source
seq.
0
– 500
20
°C*min
.
3532
Restart lock
0
– 1800
300
S
3533
Switch on delay
0
– 120
5
Min.
3534
Forced time basic
stage
0
– 1200
60
S
3540
Auto source seq.
ch’over
----/10
– 990
500
H
3541
Auto source seq.
exclusion
None, First producer, last producer,
first and last producer
None
3544
Leading source
Producer 1, Producer 2, Producer 3,
Producer 4, Producer 5, Producer 6,
Producer 7, Producer 8, Producer 9,
Producer 10, Producer 11, Producer
12, Producer 13, Producer 14,
Producer 15, Producer 16
Producer 1
3560
Return setpoint min
P3561
– 95
8
°C
3561
Return setpoint min
OEM
8
– P3560
8
°C
3562
Return influence
consumers
Off, On
On
3590
Temp differential min
----/0 - 20
---
°C
Buffer Storage Tank
4720
Auto generation lock
None, With B4, With B4 and B42/B41
With B4
-