11
1.
Reversing Edge device
(must be normally open contact):
Note:
If the door is controlled by any device or wired in such a manner that the door is not controlled by constant
pressure on close then an appropriate reversing edge must be installed.
2.
External interlock:
Remove jumper between terminals 1 and 2 and wire interlock between these two
terminals.
3.
Radio control receiver
: Wire standard radio receiver to separate radio strip on side of control box or to terminals 7, 8
and 9 on control terminal strip inside control box.
4.
Single button open/close device:
Wire to terminals 7 and 8 on control terminal strip.
5.
Loop detectors, standard photocells (with a N.O. contact) and other reversing devices:
Wire to terminals 3 and 6
on control terminal strip.
IMPORTANT:
PHOTOCELLS MUST BE MOUNTED NO HIGHER THAN 6” OFF THE FLOOR.
6.
24 Volt power
: Wire to terminals 1 and 9 on control terminal strip
CONNECTION OF A REVERSING EDGE DEVICE AND CONTROL ACCESSORIES