background image

 

16 

For 3-phase operators: If door moves in wrong direction, turn off incoming power and reverse any two of the three 
incoming power supply leads to correct rotation. Press the on board open button again. If door is going in the correct open 
direction, activate the open limit switch to ensure door stops. If door does not stop, turn off incoming power and 
interchange any two incoming power lines once again and slide dipswitch #1 to reverse motor direction. If motor direction 
is reversed, the open and close limit switches are automatically reversed. However, the advanced close limit switch needs to 
be manually changed. To do this, disconnect the 2 wires from the advanced limit switch and re-connect to the auxiliary limit 
switch provided.   

Note

: Ensure that when the on-board open button is depressed and the door moves in the correct open direction that 

activation of the open limit switch illuminates the “OPEN LIMIT’’ L.E.D and stops the door. 

 
 
 
 
 
 
 
 
 

LIMIT SWITCH ADJUSTMENTS: 

Once the motor rotation and limit cam direction have been verified, adjust the limit cam settings. Please note that when 
each limit switch is activated the corresponding LED will light up. Refer to operator installation manual for complete limit 
switch adjustment instructions. 
 

CONNECTION OF EXTERNAL O/C/S PBS: 

 Connect O/C/S PBS as shown in diagram. 
 Note: Jumper #1 must be removed after the external O/C/S PBS has been installed. 
 
 
 
 
 
 
 
 
 
 
 

FAILSAFE FEATURE 

A safety device failsafe feature is built into the logic board. The logic board has provisions to connect one primary 
monitored safety device as well as 1 or more secondary non-monitored safety device(s). 
 

Primary monitored safety device: 

MICANAN monitored failsafe photo beams or MICANAN compatible monitored failsafe devices must be connected to 
terminals P1 and P2 as primary monitored safety device. Primary monitored safety device must be connected if momentary 
activation on close is required in B2, T and TS modes. If it is not connected in B2, T and Ts modes, door can only be closed by 
constant pressure on close and if constant pressure is removed before door reaches full close position, door reverses to full 
open. 
Note: Only one monitored failsafe device can be connected to terminals P1 and P2. 
 
 
 

 
 
 
 
 
 

 

Summary of Contents for PRO-GH

Page 1: ...INSTALLATION AND INSTRUCTION MANUAL MODELS PRO GH PRO GHC AUG 2010...

Page 2: ...0 OPERATOR MAINTENANCE ____________________________________________________ 31 MECHANICAL DRAWINGS AND PARTS LISTS _____________________________________ 32 ELECTRICAL DIAGRAMS ________________________...

Page 3: ...x Door Sprocket 50B23 x 1 or 1 1 4 bore 2 set screws and x 1 1 4 keyway for sectional doors or 50B40 x 1 or 1 1 4 bore 2 set screws and x 1 1 4 keyway for rolling doors Note Sprocket size and bore ma...

Page 4: ...rd Smart 10 0 UL325 2010 compliant Note Micanan compatible primary entrapment device must be connected for B2 T or TS momentary or timer activation on close feature Option 2 Relay logic controls with...

Page 5: ...door system READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS Commercial door operators are never to be installed on a residential installation Install only on a properly operating and balanced door A doo...

Page 6: ...on opposite side of drive shaft For both the PRO GH and PRO GHC operators the handing of the operator should be stated at time of order Depending on installation if handing of chain hoist is not corre...

Page 7: ...shaft is approximately 12 30cm to 15 38cm The operator may be wall bench mounted or bracket shelf mounted These two mounting configurations are shown below 4 Mount the operator to the wall hood or be...

Page 8: ...s floor Cut chain and connect so that chain is 2 to 3 from the floor 11 Install chain keeper to wall near hand chain at approximately 4 from floor Run disconnect chain through keyhole of chain keeper...

Page 9: ...10V WW MSL100 220V WW MSLC100 WW MSL300 WW or MSLC300 WW in the electrical drawings section at the end of this manual Refer to electrical diagrams inside control box cover or at the end of this manual...

Page 10: ...moving parts of door or hardware Install Entrapment warning sign next to control station Connect 3 button open close stop push button station to terminals 2 3 4 and 5 Refer to electrical diagram for c...

Page 11: ...iver Wire standard radio receiver to separate radio strip on side of control box or to terminals 7 8 and 9 on control terminal strip inside control box 4 Single button open close device Wire to termin...

Page 12: ...le phase or 3 phase Connect open close stop push button station to terminals T2 stop T3 common T4 open and T6 temporary CP on close 3 Verify motor direction After the electrical power connections are...

Page 13: ...imits Remove blue wire from advanced open limit and place it on N O pin of advanced close limit 4 Adjust limit switch cams Using the open close stop push button station move door to fully closed and f...

Page 14: ...fety device can be connected to terminals S1 and S2 Important Do not remove resistor that is factory installed across terminals S1 and S2 unless installing a 4 wire electric edge 4 wire electric edge...

Page 15: ...inal strip must remain connected MOTOR DIRECTION VERIFICATION Make sure the mode of operation is selected to D1 After electrical power connections are made manually move door to mid position Using the...

Page 16: ...irection have been verified adjust the limit cam settings Please note that when each limit switch is activated the corresponding LED will light up Refer to operator installation manual for complete li...

Page 17: ...ernal single button as shown in diagram Please refer to Modes of operation for the functionality of single button MODES OF OPERATION All operators leave the factory in the D1 mode setting please read...

Page 18: ...Momentary contact from mid stop opens the door to full open position Constant activation when door is opening bypass mid stop if enabled Close button Constant pressure on close Door reverses to full o...

Page 19: ...ivation reverses the door Momentary activation refreshes the timer to close Timer to close Closes the door from mid stop or full open Momentary activation of stop button will de activate the timer Tim...

Page 20: ...ted in C2 D1 E2 and T modes of operation Delay on close timer is OFF when the Delay on close dial is set to OFF position To adjust this timer rotate the dial clockwise to the desired value The minimum...

Page 21: ...itter Repositioning antenna may provide greater range 8 Repeat transmitter programming steps for additional transmitters OPERATION 1 Press and release the button on MICANAN transmitter 2 Receiver LED...

Page 22: ...LED Status Cause Fault ON Primary safety devices not connected to P1 P2 or not functioning properly Safety devices are activated 10k Ohm resistor between S1 S2 removed or faulty Fault Blinking Interlo...

Page 23: ...eversing door when door is almost fully closed To adjust door travel 1 Open cycle Depress cam plate and spin Open limit cam away from Open limit switch to increase door travel or spin Open limit cam t...

Page 24: ...eam disconnect all power to door operator to prevent unintended operation and have the door full open or close 4 Do not reconnect power to the door or gate operator until instructed to do so 5 Only in...

Page 25: ...nnect these paired wires to the P1 and P2 terminals on the logic board or interface module if applicable as shown in Figure 3 Use minimum 18 gauge wires and secure the wires to wall or ceiling MICANAN...

Page 26: ...gning the photo beams 1 Turn the power on to the operator If the transmitter and receiver are installed properly the lights on both the transmitter red L E D and receiver green L E D will be ON 2 If t...

Page 27: ...ting Nut make sure to secure input shaft to not allow shaft to rotate when tightening or loosening nut 4 Gradually tighten clutch nut until the tension is sufficient to permit clutch to drive door smo...

Page 28: ...e with operator drive chain Slide stabilizing rod through slot of engagement arm and attach to frame or external support to prevent arm from rotating during operation Note Location of arm and stabiliz...

Page 29: ...o decrease nylon lock nut on brake spring bolt Observe solenoid during electrical testing of brake Brake spring tension must be adjusted so that solenoid should pull and release smoothly and quietly T...

Page 30: ...f operator is supplied with optional floor level disconnect lever Pull disconnect lever downwards and lock in place by bending lever around bracket lip as shown 3 Operate door by pulling on hand chain...

Page 31: ...5 Verify that motor solenoid and operator runs smoothly and quietly Every 6 months 1 Verify tightness of all fasteners and set screws 2 Verify that operator is properly secured 3 Inspect manual disco...

Page 32: ...32...

Page 33: ...33 33...

Page 34: ...34...

Page 35: ...35 35...

Page 36: ...36 36...

Page 37: ...37...

Page 38: ...38...

Page 39: ...39...

Page 40: ...40...

Page 41: ...41...

Page 42: ...42...

Page 43: ...43...

Page 44: ...44...

Page 45: ...hat materials and workmanship are free from defects for a period of two years from the date of invoice Materials returned to Micanan deemed defective after examination will be returned at the option o...

Reviews: