16
10
Auto restart when
over temperature
occurs
Restart disable (default)
Restart enable
11
Beeps while primary
source is interrupted
Alarm on (default)
Alarm off
12
Low power power
saving
Power Saving OFF
(default)
Power Saving ON
13
Overload bypass:
When enabled, the
unit will transfer to
line mode if overload
occurs in battery
mode.
Bypass disable (default)
Bypass enable
14
Buzzer mute setting
Buzzer on (default)
Buzzer off
15
Low DC cut-off
voltage:
•
If battery power is
only power source
available, inverter
will shut down.
•
If PV energy and
battery power are
available, inverter
will charge battery
without AC output.
If PV energy, battery
power and utility are
all available, inverter
will transfer to line
mode and provide
output power to
loads.
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 23.0V
Set Range : 22-26V
3KW 48VDC/5KW 48VDC
Default setting : 46.0V
Set Range : 44-52V
When the battery definition mode is AGM (lead-acid battery type), FLD
(water injection battery type) mode:the setting point in program 17.
3KW 24VDC
default setting : 23.0V
Set Range: 22-26V
3KW 48VDC/5KW 48VDC
Default setting : 46.0V
Set Range : 44-52V
When the battery definition mode is UB (lithium battery type) mode:
the
setting point in program 17.
3KW 24VDC
Default setting : 23.8V
Set Range : 20-25V
3KW 48VDC/5KW 48VDC
Default setting : 47.6V
Set Range : 40-50V
16
Setting voltage point
back to battery
mode when
selecting
n
OPP" (OPP
" priority) in program
03.
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 26.0V
Set Range : 24-29V
3KW 48VDC/5KW 48VDC
Default setting : 54.0V
Set Range : 48-58V