17
When the battery definition mode is AGM (lead-acid battery type), FLD
(water injection battery type) mode:the setting point in program 17.
3KW 24VDC
Default setting : 26.0V
Set Range : 24-29V
3KW 48VDC/5KW 48VDC
Default setting : 52.0V
Set Range : 48-58V
When the battery definition mode is LIB (lithium battery type) mode: the
setting point in program 17.
3KW 24VDC
default setting : 27.2V
Set Range : 23-29V
3KW 48VDC/5KW 48VDC
Default setting : 54.4V
Set Range : 46-58V
17
Battery Type
Lead-acid batteries (default): "AGM"
Water-filled battery : ”FLD”
Lithium battery: "LIB”
Customer Setup Type : ''CUS"
18
Battery low voltage
alarm point
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 22.0V
Set Range : 21-27V
3KW48VDC/5KW48VDC
Default setting : 44.0V
Set Range : 42-54V
When the battery definition mode is LIB (lithium battery type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 23.8V
Set Range : 20.6-25V
3KW48VDC/5KW48VDC
Default setting : 47.6V
Set Range : 41.2-50V
19
Battery low voltage
shutdown point
When the battery definition mode is CUS (customer set type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 21.0V
Set Range : 20-24V
3KW 48VDC/5KW 48VDC
Default setting : 42.0V
Set Range : 40-48V
When the battery definition mode is LIB (lithium battery type) mode: the
setting point in program 17.
3KW 24VDC
Default setting : 23.0V
Set Range : 20-24V
3KW 48VDC/5KW 48VDC
Default setting : 46.0V
Set Range : 40-48V