10. Commissioning (Specialist
installer)
10.1 Before commissioning
Check all connections again:
– Condensation run-off hose correctly
installed
– Ventilation channels / ventilation
components correctly installed
– Electrical connection done in accordance
with the wiring diagram
– Jumper settings correct (if required)
10.2 Adjusting ventilation system
Check whether the factory-set volumetric
flows for the supply air and exhaust air fan
match with the volumetric flows defined by
the planner. In the case of deviations, set
the volumetric flows defined by the planner
for the supply air and exhaust air fan, using
the 6 potentiometer adjusters.
DANGER
Danger to life from electric
shock. Control circuit board
and room air control are
still powered up even if the
front cover is opened.
Behave in a security and
safety-conscious way in the
area of the control circuit
board.
Remove the screws at the front of the
electrical connection box. Swing the cover
upwards.
Adjust the total volumetric flows for the
individual ventilation levels using the 6
potentiometer adjusters on the control
circuit board. Refer to Chapter 10.3 to 10.4
for adjustment values and adjustment
options:
– Supply air: Ventilation levels 1, 2 and 3
with the blue potentiometer adjusters
– Exhaust air: Ventilation levels 1, 2 and 3
with the red potentiometer adjusters
S.. Potentiometer adjusters
Install all the supply air and exhaust air
valves, ventilation grilles and wall overflow
elements pre-defined by the planner.
Adjust the ventilation system with these
elements:
– Switch the ventilation unit on at the room
air control, see Chapter 5.
– Select ventilation level 2.
– Adjust the planned partial volumetric flow
for all rooms.
If necessary, correct the total volumetric
flows at the potentiometer adjusters, as
described before.
Swing the electrical terminal box cover
downwards and secure it with the screw.
Start the ventilation unit up only
after installation is complete and
the control circuit board cover is
in place.
i
Supply air Exhaust air
Summary of Contents for aeronom WR 600
Page 6: ...4...
Page 50: ...48 15 Anhang Verdrahtungsplan...
Page 52: ...50...
Page 56: ...54 Exhaust air Supply air Outgoing air Outside air...
Page 100: ...98 15 Appendix Wiring diagram...
Page 102: ...100...
Page 106: ...104 Air sortant Air entrant Air rejet Air ext rieur...