95
11. Accessories
Accessory / Product type
WR 600
Article no.
4x air filter, filter class G4
WSG 600-1
0093.0688
2x air filter, filter class G4 and
1x air filter, filter class F7
WSF 600
0093.0689
Room air control RLS 1 WR
RLS 1 WR
0157.0809
Room air control RLS D1 WR
RLS D1 WR
0157.0828
CO
2
sensor
SKD
0157.0345
Summer cassette
WRSK 600
0095.0153
Hygrostat
HY 5
0157.0123
Thermostat
TH 10
0157.0764
Air flow monitor
LW 9
0157.0779
Universal contactor
US16 T
0157.0769
Filter box
TFE 25-4
0149.0079
Electric air heater
DRH 25-6
0082.0107
Electric air heater
ERH 25-2
0082.0104
VOC sensor (air quality controller)
EAQ 10/2
0157.0834
Recommendation for the outside air inlet
In passive-energy houses, suitable
outside air pre-heating is vitally
important, in order to ensure
continuous operation.
One of the following components must be
used:
a brine earth heat exchanger
or
a WRH + TH 10 hydraulic heat register
(see heat register connection diagram)
or
a DRH 25-6 electrical air LW 9 +
TH 10 + US 16 T (see Chapter 9.6.5,
Connection option 7)
Recommendation for the supply air duct
If the ventilation unit is installed with a
hydraulic re-heating register (supply
air) in a passive energy house, a
thermostat (TH 10) has to be installed
to protect against supply air that is too
cold.
Use a TH 10 thermostat in the supply air duct
as a safety device for the WRH water-using
re-heating register. This switches the ventila-
tion unit off if the supply air temperatures
drop too low, (see Chapter 9.6.5, Connection
option 6) Recommendation: Switch-off tem-
perature 5 °C and differential temperature 3 K.
Connection to KNX/IEB Bus
The ventilation unit can also be operated
together with KNX/EIB bus components, e.g.
with fan coil actuators or operating panels
from the corresponding KNX supplier.
Further KNX/EIB modules can be integrated
in the system bus without problem, e.g. CO
2
sensors, timer switches and motion detectors.
i
i
Summary of Contents for aeronom WR 600
Page 6: ...4...
Page 50: ...48 15 Anhang Verdrahtungsplan...
Page 52: ...50...
Page 56: ...54 Exhaust air Supply air Outgoing air Outside air...
Page 100: ...98 15 Appendix Wiring diagram...
Page 102: ...100...