3.10.3.7
Example for Scaling of Analog Display Ranges
Voltage A-B is selected as the measurand to be transmitted by channel A-1.
The measuring range is from 0 to 1.5 V
nom
with V
nom
= 100 V.
The range to be transmitted is from 0.02 to 1 V
nom
with the associated display
range from 4 mA to 18 mA.
The knee-point of the characteristic is 0.1 V
nom
with an associated display of
16 mA.
Measurands
Range
Measurands of the variable Mx
0 V ... 150 V
Associated scaled measurands
0 ... 1
Measurands to be output
Range
Measurands with knee-point to be output
2 V ...10 V... 100 V
Associated scaled measurands
0.013 ... 0.067 ... 0.67
with:
Mx,scal,min = (2 V - 0 V ) / (150 V - 0 V ) = 0.013
Mx,scal,knee = (10 V - 0 V ) / (150 V - 0 V ) =
0.067
Mx,scal,max = (100 V - 0 V ) / (150 V - 0 V ) =
0.67
Measurands
Analog display values
Measurands in the range "Measurands to be
output"
0.02 ... 0.1 V
nom
... 1 V
nom
4 mA ... 16 mA ... 18 mA
In this example the following P631 settings are selected in the menu branch
Parameter/Config. parameters:
P631
3 Operation
3-54
P631/EN M/R-11-C // P631-310-650
Summary of Contents for P631
Page 2: ......
Page 4: ......
Page 7: ...Changes after going to press...
Page 8: ......
Page 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Page 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Page 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Page 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Page 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Page 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Page 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Page 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Page 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Page 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Page 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Page 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Page 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Page 637: ......