Parameter
Address
Default
Min
Max
Unit
Logic Diagram
[spacer]
COMM1: Dead time monitoring
003 176
1: Yes
Fig. 3-7, (p. 3-12)
Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)
[spacer]
The P631 monitors telegram transmission to make sure that no excessive pause
occurs within a telegram. This monitoring function can be disabled if it is not
required.
Note: This setting is only necessary for modem transmission.
[spacer]
COMM1: Mon. time polling
003 202
25
3
254
s
Fig. 3-7, (p. 3-12)
Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)
[spacer]
The time between two polling calls from the communication master must be less
than the time set here.
[spacer]
COMM1: Octet comm. address
003 072
1
0
254
Fig. 3-7, (p. 3-12)
Fig. 3-8, (p. 3-13)
Fig. 3-9, (p. 3-14)
Fig. 3-10, (p. 3-15)
Fig. 3-11, (p. 3-16)
Fig. 3-12, (p. 3-17)
[spacer]
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be selected
for both addresses.
“ASDU”: Application Service Data Unit
[spacer]
COMM1: Oct.2 comm.addr.DNP3
003 240
0
0
255
[spacer]
In the DNP 3.0 protocol, a 16-bit address is used to identify devices.
The address that can be set here is the higher-order octet, whereas the address
set at COMM1: Octet comm. address is the lower-order octet of the
DNP address.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
P631
7 Settings
7-18
P631/EN M/R-11-C // P631-310-650
Summary of Contents for P631
Page 2: ......
Page 4: ......
Page 7: ...Changes after going to press...
Page 8: ......
Page 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Page 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Page 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Page 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Page 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Page 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Page 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Page 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Page 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Page 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Page 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Page 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Page 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Page 637: ......