Parameter
Address
Default
Min
Max
Unit
Logic Diagram
[spacer]
IDMT2: Release neg PSx
081 126
082 126
083 126
084 126
1: Without delay
[spacer]
Setting for the reset characteristic (negative-sequence current system).
[spacer]
IDMT1: Iref,N PSx
081 061
082 061
083 061
084 061
Blocked
0.01
0.80
Inom
[spacer]
IDMT2: Iref,N PSx
081 181
082 181
083 181
084 181
Blocked
0.01
0.80
Inom
[spacer]
Setting for the reference current (residual current system).
[spacer]
IDMT1: Iref,N dynamic PSx
081 062
082 062
083 062
084 062
Blocked
0.01
0.80
Inom
[spacer]
IDMT2: Iref,N dynamic PSx
081 182
082 182
083 182
084 182
Blocked
0.01
0.80
Inom
[spacer]
Setting for the reference current (residual current system) in dynamic mode.
This operate value is only effective while the hold time for dynamic parameters
is elapsing.
[spacer]
IDMT1: Characteristic N PSx
081 063
082 063
083 063
084 063
0: Definite Time
[spacer]
IDMT2: Characteristic N PSx
081 183
082 183
083 183
084 183
0: Definite Time
[spacer]
Setting for the tripping characteristic (residual current system).
[spacer]
IDMT1: Factor kt,N PSx
081 064
082 064
083 064
084 064
1.00
0.05
10.00
[spacer]
IDMT2: Factor kt,N PSx
081 184
082 184
083 184
084 184
1.00
0.05
10.00
[spacer]
Setting for the kt,N factor of the starting characteristic (residual current system).
[spacer]
IDMT1: Min. trip t. N PSx
081 067
082 067
083 067
084 067
1.00
0.00
10.00
s
[spacer]
IDMT2: Min. trip t. N PSx
081 187
082 187
083 187
084 187
1.00
0.00
10.00
s
[spacer]
Setting for the minimum trip time characteristic (residual current system).
[spacer]
IDMT1: Hold time N PSx
081 065
082 065
083 065
084 065
0.00
0.00
600.00
s
[spacer]
IDMT2: Hold time N PSx
081 185
082 185
083 185
084 185
0.00
0.00
600.00
s
[spacer]
Setting for the hold time for storing the starting time once the starting has
dropped out (residual current system).
7 Settings
P631
P631/EN M/R-11-C // P631-310-650
7-117
Summary of Contents for P631
Page 2: ......
Page 4: ......
Page 7: ...Changes after going to press...
Page 8: ......
Page 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Page 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Page 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Page 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Page 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Page 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Page 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Page 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Page 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Page 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Page 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Page 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Page 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Page 637: ......