Parameter
Address
Default
Min
Max
Unit
Logic Diagram
Thermal overload
protection
THRM1: Status replica, TH1
004 150
Not measured
-25000
25000
%
[spacer]
Display of the buffer content of the thermal overload protection function.
[spacer]
THRM1: Object temperat.,TH1
004 151
Not measured
-40
300
°C
[spacer]
Display of the temperature of the protected object as determined by function
THRM1.
[spacer]
THRM1: Coolant temp. TH1
004 154
Not measured
-40
200
°C
[spacer]
Display of the coolant temperature of the protected object.
Depending on the setting at THRM1: Select CTA PSx
or THRM2: Select CTA PSx for coolant temperature acquisition, one of the
following values will be displayed:
●
Setting
Default temp. value
: Display of the set temperature value.
●
Setting
From PT100
: Display of the temperature measured by the
resistance thermometer.
●
Setting
From 20 mA input
: Display of the temperature measured via the
20 mA input.
[spacer]
THRM1: Pre-trip t. left,TH1
004 153
Not measured
0.0
1000.0
min
[spacer]
Display of the time remaining before the thermal overload protection function
THRM1 will reach the tripping threshold.
[spacer]
THRM1: Stat. repl., p.u.TH1
004 204
Not measured
-25.00
25.00
[spacer]
Display of the buffer content of the thermal overload protection function THRM1
referred to a buffer content of 100%.
[spacer]
THRM1: Object temp. p.u. 1
004 205
Not measured
-0.40
3.00
100°C
[spacer]
Display of the temperature of the protected object referred to 100°C.
[spacer]
THRM1: Coolant temp. p.u. 1
004 206
Not measured
-0.40
2.00
100°C
[spacer]
Display of the coolant temperature of the protected object referred to 100°C.
P631
8 Information and Control Functions
8-10
P631/EN M/R-11-C // P631-310-650
Summary of Contents for P631
Page 2: ......
Page 4: ......
Page 7: ...Changes after going to press...
Page 8: ......
Page 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Page 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Page 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Page 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Page 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Page 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Page 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Page 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Page 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Page 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Page 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Page 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Page 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Page 637: ......