Parameter
Address
Default
Min
Max
Unit
Logic Diagram
Binary and analog
output
OUTP: Reset latch. USER
021 009
0: don't execute
[spacer]
Reset of latched output relays from the user interface.
[spacer]
OUTP: Relay assign. f.test
003 042
060 000: MAIN: Without function
[spacer]
Selection of the relay to be tested.
[spacer]
OUTP: Relay test
003 043
0: don't execute
[spacer]
The relay selected for testing is triggered for the duration set at OUTP: Hold-
time for test.
[spacer]
OUTP: Hold-time for test
003 044
1
1
10
s
[spacer]
Setting for the time period for which the selected output relay is triggered for
functional testing.
Parameter
Address
Default
Min
Max
Unit
Logic Diagram
Measured data
output
MEASO: Reset output USER
037 116
0: don't execute
[spacer]
Resetting the measured data output function.
8 Information and Control Functions
P631
P631/EN M/R-11-C // P631-310-650
8-87
Summary of Contents for P631
Page 2: ......
Page 4: ......
Page 7: ...Changes after going to press...
Page 8: ......
Page 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Page 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Page 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Page 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Page 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Page 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Page 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Page 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Page 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Page 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Page 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Page 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Page 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Page 637: ......