Parameter
Address
[spacer]
SFMON: Mutex deadlock
093 032
[spacer]
Software threads are locked from each other by mutex. If this error occurs
during a (re-)start of the device then this message is displayed and the device is
blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Invalid memory ref.
093 033
[spacer]
Attempt to access an invalid memory segment. If this error occurs during a
(re-)start of the device then this message is displayed and the device is blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Unexpected exception
093 034
[spacer]
Miscellaneous error message from the processor or operating system. If this
error occurs during a (re-)start of the device then this message is displayed and
the device is blocked.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Invalid arithm. op.
093 011
[spacer]
Invalid arithmetic operation.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Undefined interrupt
093 012
[spacer]
Undefined interrupt.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
[spacer]
SFMON: Exception oper.syst.
093 013
[spacer]
Interrupt of the operating system.
1st device reaction: Warm restart
2nd device reaction: Device blocking
'Warning' output relay: Yes
'Blocked/faulty' output relay: Yes
11 Troubleshooting
P631
P631/EN M/R-11-C // P631-310-650
11-7
Summary of Contents for P631
Page 2: ......
Page 4: ......
Page 7: ...Changes after going to press...
Page 8: ......
Page 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Page 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Page 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Page 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Page 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Page 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Page 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Page 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Page 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Page 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Page 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Page 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Page 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Page 637: ......