Parameter
Address
[spacer]
SFMON: Iref, b inval. range
091 008
[spacer]
The reference current determined by the P631 for differential protection is not
within the permissible range.
Device reaction: Protection is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: Matching fail. end a
091 000
[spacer]
SFMON: Matching fail. end b
091 001
[spacer]
The calculated amplitude matching factor of the differential protection function
is above the permissible range.
Device reaction: Protection is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: Ratio mtch.fact.inv.
091 004
[spacer]
The ratio of the amplitude matching factors for differential protection is not
within the permissible range.
Device reaction: Protection is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: 2nd match.fact. inv.
091 006
[spacer]
The second highest amplitude matching factor for differential protection is
smaller than permitted.
Device reaction: Protection is blocked.
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
[spacer]
SFMON: CTA error THRM1
098 036
[spacer]
Faulty coolant temperature acquisition.
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: Setting error THRM1
098 038
[spacer]
The maximum permissible object temperature and the maximum permissible
coolant temperature have been set to the same value. This setting is not valid.
'Warning' output relay: Yes
'Blocked/faulty' output relay: –
[spacer]
SFMON: Inv.inp.f.clock sync
093 120
[spacer]
The function was configured to a binary signal input on the analog I/O module Y.
Such a configuration is not permitted for this function.
Device reaction:
'Warning' output relay: Updating
'Blocked/faulty' output relay: –
11 Troubleshooting
P631
P631/EN M/R-11-C // P631-310-650
11-11
Summary of Contents for P631
Page 2: ......
Page 4: ......
Page 7: ...Changes after going to press...
Page 8: ......
Page 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Page 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Page 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Page 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Page 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Page 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Page 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Page 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Page 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Page 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Page 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Page 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Page 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Page 637: ......