3.4.3.1
COMM2 – Checking Spontaneous Signals
It is possible to select a signal for test purposes. The transmission of this signal to
the control station as ‘sig. start‘ or ‘sig. end‘ can then be triggered via the local
control panel.
48Z50FLA
COMM2:
Test spont.sig. end
[ 103 186 ]
Selected signals
Signal 1
Signal 2
Signal 3
Signal n
1: execute
0: don't execute
0
1
1: execute
0: don't execute
0
1
COMM2:
Test spont.sig.start
[ 103 184 ]
COMM2:
Sel.spontan.sig.test
[ 103 180 ]
COMM2:
Spontan. sig. start
[ --- --- ]
COMM2:
Spontan. sig. end
[ --- --- ]
Fig. 3-15: COMM2 – Checking spontaneous signals.
P631
3 Operation
3-20
P631/EN M/R-11-C // P631-310-650
Summary of Contents for P631
Page 2: ......
Page 4: ......
Page 7: ...Changes after going to press...
Page 8: ......
Page 16: ...P631 Table of Contents 8 P631 EN M R 11 C P631 310 650...
Page 56: ...P631 2 Technical Data 2 28 P631 EN M R 11 C P631 310 650...
Page 236: ...P631 3 Operation 3 180 P631 EN M R 11 C P631 310 650...
Page 246: ...P631 4 Design 4 10 P631 EN M R 11 C P631 310 650...
Page 266: ...P631 5 Installation and Connection 5 20 P631 EN M R 11 C P631 310 650...
Page 276: ...6 8 Configurable Function Keys P631 6 Local Control HMI 6 10 P631 EN M R 11 C P631 310 650...
Page 548: ...P631 10 Commissioning 10 10 P631 EN M R 11 C P631 310 650...
Page 568: ...P631 12 Maintenance 12 8 P631 EN M R 11 C P631 310 650...
Page 570: ...P631 13 Storage 13 2 P631 EN M R 11 C P631 310 650...
Page 572: ...P631 14 Accessories and Spare Parts 14 2 P631 EN M R 11 C P631 310 650...
Page 576: ...P631 15 Order Information 15 4 P631 EN M R 11 C P631 310 650...
Page 582: ...P631 A2 Internal Signals A2 4 P631 EN M R 11 C P631 310 650...
Page 608: ...P631 A4 Telecontrol Interfaces A4 18 P631 EN M R 11 C P631 310 650...
Page 637: ......