MICOM SWING SW & SWSP
Installation Manual
Page
30
NOTE: The Control Unit does not have the Monitoring function activated when it leaves the factory.
In order to activate it, parameters 18, 19 or 35 need to be programmed - depending upon which
sensor we want to Monitor in the Control Unit
(see section “12.-PROMGRAMMING OF THE
CONTROL UNIT”).
Parameter 18 activates the Monitoring of the sensors connected to P10 (Closing Safety), Parameter
19 P9 (internal sensor).
Parameter 35 activates the Monitoring of the sensors connected to P14 (Opening Safety).
P3 is connection of the Monitoring signal of multiple sensors. i.e : safety when closing, movement or
safety when opening.
9.4 P4 Connector. Emergency Stop
The P4 connector is an input used for connection to the emergency stop device. This input is
programmed when leaving the factory to work with Normally Open contacts (NO), but can be
programmed to work with Normally Closed contacts (NC), (plea
se see section “13 -
PROGRAMMING PARAMETRES” - Parameter Nº22”).
When this input is activated the door will immediately stop.
9.5 P13 Connector. Emergency Open/Close
This input is connected mainly to the fire alarm and anti-panic systems and its function is to Open or
Close the door in any situation, except when the function selector is in the position of CLOSED or
MANUAL.
This input is programmed at the factory so that it works with Normally Open (NO) contacts. The door
can open but it can be programmed to function with Normally Closed (NC) contacts, or for the door to
close
(see section “13.-PROGRAMMING PARAMETRES” - Parameter Nº32”).
9.6 P5 Connector. Night Bank / Switch
Its function is to Open the door in whatever situation, including a power cut (battery optional).
In the event of a fault in the general electricity supply, this signal can open the door by making use of
an emergency battery (this battery is optional and is not included in the operator).
This input has priority over the function selector.
This input only works with Normally Open (NO) contacts.
9.7. P6 Connector. E-Lock or Automatic Bolt (Lock) 24Vdc
The P6 connector is a 24Vdc output.
NOTICE!
Never go over the maximum consumption. If so the control unit will be damaged. The
maximum consumption is 7W (300mA).
Automatic alternating current bolts are not allowed; their use provokes severe damage to the control
unit. Only automatic bolts that work with direct current can be connected. Special attention should be
paid to the voltage value; in the event of placing an automatic bolt that is different from 24V, the
control unit will be damaged.