MICOM SWING SW & SWSP
Installation Manual
Page
47
21
Safety Sensor Input (Closing Side)
0 or 1
1
Value 0 = NO (Normally Open)
Value 1 = NC (Normally Closed)
22
Emergency Stop Input
0 or 1
0
Value 0 = NO (Normally Open)
Value 1 = NC (Normally Closed)
23
NIGHT BANK / Switch
0
Value 0 = Emergency Opening Mode NO (Normally Open)
24
Low Energy System (Low Kinetic Energy)
From 0 to 6
0
Value 0 = System deactivated.
Value 1 = Activated. Weight of the lower panel or equal to 50Kg.
Value 2 = Activated. Weight of the lower panel or equal to 60Kg.
Value 3 = Activated. Weight of the lower panel or equal to 70Kg.
Value 4 =Activated. Weight of the lower panel or equal to 80Kg.
Value 5 = Activated. Weight of the lower panel or equal to 90Kg.
Value 6 =Activated. Weight of the lower panel or greater than
90Kg.
25
Acoustic warning at the entrance
From 0 to 3
0
Value 0 =Deactivated warning.
Value 1 =Warning lasting 1 second.
Value 2 =Warning lasting 2 seconds.
Value 3 =Warning lasting 3 seconds.
26
Battery Monitoring
From 0 to 2
0
Value 0 = No Battery.
Value 1 =Monitoring Activated
Value 2 = Monitoring Deactivated
27
Reserved
Not available
28
Closing Force after Deceleration
From 0 to 5
1
Value 0 = Low
Value 1 =Medium-Low
Value 2 = Medium
Value 3 = Medium-High
Value 4 = High (recommended in areas of high winds)
Value 5 = Very High (recommended in areas of high winds)
29
Opening Force after Deceleration (motor damping effect)
From 0 to 5
2
Value 0 = Low (recommended when using Push&Go system)
Value 1 = Medium-Low
Value 2 = Medium
Value 3 = Medium-High