Micon M1500-600/150kW 50Hz
Manual
UK1500.PM6
Rev. 95-06-23 OKK
Electronic control
3
Fault code table
3.6
3
21 MANUAL STOP
ALARM DELAY (S)
RESET LEVEL
MAX ERROR/HOUR
YAWING
ALARM
+ = Activates a response
/ = No response
- = Prevents a response
M = Manual control from the mill
F = Remote control via management system
A = Automatic
P = Parameter
20
NO. TEXT
00 PARAMETER ERROR
01 VIBRATION
02 THERMO. HYD. MOTOR
03 THERMO YAW MOTOR
04 G1 HOT
05 CABLE TWISTED
06 WP - 2050 FAULT
07 HYD. PUMP ERROR
08 OVERVOLTAGE
09 UNDERVOLTAGE
10 FREQUENCY FAULT
11 ROT. RPM >LIMIT
12 ROTOR TACHO DEF.
13 BRAKE WORN OUT
14 BRK. NOT RELEASED
15 GEN. TACHO DEF.
16 ANENOMETER DEF.
17 AUTOREWIND
18 OVERWIND
19 GRID DROP
20 STOP BY DATALINE
0
0,3
1
1
10
10
0,5
15
XX/0,5
XX
0.1-0.9
2/3 rpm.
120
10
4/0,5
3xR_rpm.
0-9999M
0,1
30
0
0
0
+
+
+
+
+
+
/
+
/
/
/
+
+
+
+
+
+
/
/
/
-
-
+
+
+
-
+
-
+
+
+
+
+
+
+
+
+
+
+
-
+
-
+
/
/
/
/
/
1
/
1
1
2
2
2
1
1
/
3
1
1
1
1
5
/
/
M
M
M
M
A
M
A
A
A
A
A
M
F
M
A
F
A
A
A
A
F
M
CAUSE
Parameter check sum error
TERM (01) = 0
TERM (18) = 0
TERM (03) = 0
TERM (02) = 0 / TERM (30) = 0
TERM (06) = 0
TERM (14) = 0 + (G1 or G2) - BYPASS
TERM (17) = 0
Grid volt. high/extra high
Grid voltage low
Grid frquency deviating
High rotor RPM
Rotor RPM < 15 - BYPASS
Term (05) = 0
Term (13) = 0 and Brake free
Wind > x + Gen. RPM<200 + Rot. RPM > 15
P > 20 kW + Vind < 1 m/s
SNO > 4 / (SNO = 3 + P < 20kW)
Vind (10 min) > xx m/s
Voltage drop to WP - 2000
Stop - command from man. sys.
Stop by keypad / stop - button