4
MICRO AIR
®
FRP
CLEAN AIR SYSTEMS
MODEL FRP SPECIFICATIONS
CABINET DIMENSIONS:
FRP4
72” H x 53” W x 48” D
FRP6
92” H x 53” W x 48” D
FRP6-2
94” H x 95” W x 48” D
FRP6-3
94” H x 136” W x 48” D
FRP8
112” H x 53” W x 48” D
FRP8-2
114” H x 95” W x 48” D
FRP8-3
114” H x 136” W x 48” D
FRP8-4
114” H x 179” W x 48” D
Add 64” to height for long legs and 16” for short legs.
FILTER AREA:
FRP4
600-1000 square feet
FRP6
900-1500 square feet
FRP6-2
1800-3000 square feet
FRP6-3
2700-4500 square feet
FRP8
1200-2000 square feet
FRP8-2
2400-4000 square feet
FRP8-3
3600-6000 square feet
FRP8-4
4800-8000 square feet
Lower number is for PTFE and Spunbond fi lters, higher
number is for all other media types.
INPUT VOLTAGE:
120V 60Hz 1 phase
208-230V / 460V 60Hz 3 Phase
MAXIMUM CURRENT:
Pulse Only
1 Amp
5HP
208V:
13.6
Amps
230V:
11.8
Amps
460V:
5.9
Amps
7.5HP
208V:
19.4
Amps
230V:
18.0
Amps
460V:
9.0
Amps
10HP
208V:
24.9
Amps
230V:
23.6
Amps
460V:
11.8
Amps
15HP
208V:
36.8
Amps
230V:
34.0
Amps
460V:
17.0
Amps
20HP
230V:
46.0Amps
460V:
23.0
Amps
30HP
230V:
68.0
Amps
460V:
34.0
Amps
COMPRESSED AIR:
Minimum air line of 3/4 inch at 80 psi minimum and 90
psi maximum. Oil and moisture free compressed air is
required for proper operation.
Summary of Contents for FORCE FRP4
Page 13: ...FRP MICRO AIR CLEAN AIR SYSTEMS 13 FRP4 PULSE CONTROL ONLY WIRING DIAGRAM ...
Page 14: ...14 MICRO AIR FRP CLEAN AIR SYSTEMS FRP6 PULSE CONTROL ONLY WIRING DIAGRAM ...
Page 15: ...15 FRP MICRO AIR CLEAN AIR SYSTEMS FRP8 PULSE CONTROL ONLY WIRING DIAGRAM ...
Page 16: ...16 MICRO AIR FRP CLEAN AIR SYSTEMS FRP6 2 PULSE CONTROL ONLY WIRING DIAGRAM ...
Page 17: ...17 FRP MICRO AIR CLEAN AIR SYSTEMS FRP6 3 PULSE CONTROL ONLY WIRING DIAGRAM ...
Page 18: ...18 MICRO AIR FRP CLEAN AIR SYSTEMS FRP8 2 PULSE CONTROL ONLY WIRING DIAGRAM ...
Page 19: ...19 FRP MICRO AIR CLEAN AIR SYSTEMS FRP8 3 PULSE CONTROL ONLY WIRING DIAGRAM ...
Page 20: ...20 MICRO AIR FRP CLEAN AIR SYSTEMS FRP8 4 PULSE CONTROL ONLY WIRING DIAGRAM ...
Page 21: ...21 FRP MICRO AIR CLEAN AIR SYSTEMS FRP4 FULL CONTROL WIRING DIAGRAM ...
Page 22: ...22 MICRO AIR FRP CLEAN AIR SYSTEMS FRP6 FULL CONTROL WIRING DIAGRAM ...
Page 23: ...23 FRP MICRO AIR CLEAN AIR SYSTEMS FRP8 FULL CONTROL WIRING DIAGRAM ...
Page 24: ...24 MICRO AIR FRP CLEAN AIR SYSTEMS FRP6 2 FULL CONTROL WIRING DIAGRAM ...
Page 25: ...25 FRP MICRO AIR CLEAN AIR SYSTEMS FRP6 3 FULL CONTROL WIRING DIAGRAM ...
Page 26: ...26 MICRO AIR FRP CLEAN AIR SYSTEMS FRP8 2 FULL CONTROL WIRING DIAGRAM ...
Page 27: ...27 FRP MICRO AIR CLEAN AIR SYSTEMS FRP8 3 FULL CONTROL WIRING DIAGRAM ...
Page 28: ...28 MICRO AIR FRP CLEAN AIR SYSTEMS FRP8 4 FULL CONTROL WIRING DIAGRAM ...
Page 32: ...32 MICRO AIR FRP CLEAN AIR SYSTEMS THIS PAGE INTENTIONALLY LEFT BLANK ...