MODEL OM 500 SPECIFICATIONS

Input Volts: 120 VAC, 60Hz, Single Phase

208-230/460 VAC, 3-Phase (Optional)

Max. Current:

120 VAC

10.4 Amps

208-230 VAC

3.2 Amps

460 VAC

1.6 Amps

Motor:

3/4 HP TEAO

1 HP TEAO 3-Phase (Optional)

Air Flow*:

6” Inlet

665 CFM (3387 FPM)

8” Inlet

800 CFM (2292 FPM)

Dimensions:

49” H x 26” W x 14” D (without wall brackets)

Shipping Weight:

175 lbs.

Actual Weight:

155 lbs.

* All air flows are tunnel tested readings.

PACKAGE CONTENTS

1 ea.

OM 500 Unit

2 ea.

Wall Mount Brackets

1 ea.

Owner’s Manual

PRE-OPERATING INSTRUCTIONS

1.

Cut banding material and remove cardboard and plastic from unit.  Remove unit

from shipping skid.

2.

Inspect unit for shipping damage and report any damage to freight carrier.

INSTALLATION INSTRUCTIONS

A.   WALL MOUNT

   1.   Remove four 5/16” bolts from sides of cabinet near top and bottom of unit.
   2.   Use bolts removed in Step 1 to secure wall mount brackets to unit

as shown in  

FIG. 1

.

3.

Locate an installation site that will provide for the following:

A solid structure, capable of supporting the weight of the unit.

Three feet of unobstructed exhaust space from the outlet of the unit.

Easy access to service panels and unit inlet.

As near as possible to the source of oil mist unit to be captured.

FIG. 1

FIG. 2

4.

Mark location of mounting holes on the surface to which unit is to be mounted
(see 

Figure 2 

 for hole pattern).  Drill holes that are sized correctly for the

hole pattern in mounting hardware.

5.

Position the OM 500 wall mount bracket holes over the holes located on the
structure in Step 4.  Use 3/8” x 2” lag bolts or 3/8”  bolts and nuts to secure
the OM 500 to structure.

CAUTION: The size and weight of the OM 500 requires two persons or
mechanical means to lift and hold during mounting.

6.

Connect unit to oil mist source using a duct having the same diameter as
the inlet of the unit.  The duct may be flexible hose or formed sheet metal.
Maximum flow will be obtained with minimum bends in duct.  To contain oil
that will collect on the inside of the duct, the duct must be sealed.  Sloping

the duct toward the OM 500 will assist flow.  Use hose clamps or sheet
metal screws to attach duct to unit.

NOTE:

  Optional hose adapters are available for connection to 6” and 8”

diameter hose.  Use Part No. 34145-01 for 6” diameter hose, and Part No.
34145-02 for 8” diameter hose.  Attach adapter to plenum collar with sheet
metal screws and seal with RTV sealant.

B.

FLOOR MOUNT
NOTE:

  The optional base assembly (Part No. 38162-01) is required for floor

mount installation.
1.

Locate an installation site on a level surface that will meet the requirements
listed in Step 3 of the wall mounting instructions.

2.

Set the base in place and lift the unit onto the base.

CAUTION:  The size and weight of the OM 500 requires two persons
or mechanical means to lift and hold during mounting.
NOTE:

 You may want to bolt the base to the floor.

3.

Connect the unit to the oil mist source as explained in Step 6 of the wall

mounting instructions.

C.

CEILING MOUNTING
NOTE:

  The optional ceiling mounting kit (Part No. 38088-02) is required for ceiling

mount installation.
1.

Remove the two (2) 5/16” bolts from the side of the cabinet at

2.

Use the bolts removed in Step 1 to secure the ceiling mount brackets to the
unit as shown in 

FIG. 3

.

2

OM500

Summary of Contents for OM 500

Page 1: ...Model OM 500 OWNER S MANUAL CAUTION Read complete instructions before operating Please file for future reference AIR CLEANERS ...

Page 2: ... 4 Use 3 8 x 2 lag bolts or 3 8 bolts and nuts to secure the OM 500 to structure CAUTION The size and weight of the OM 500 requires two persons or mechanical means to lift and hold during mounting 6 Connect unit to oil mist source using a duct having the same diameter as the inlet of the unit The duct may be flexible hose or formed sheet metal Maximum flow will be obtained with minimum bends in du...

Page 3: ...ly circuit to this unit See Wiring Diagram FIG 6 2 Remove the front motor compartment access cover 3 Remove the electrical wiring box cover 4 Make electrical connections to the input wires as shown in Wiring Diagram FIG 6 for three phase wire connections NOTE The filter change indicator light circuit must be supplied with no more than 270V If a 460V 3 wire source is used a transformer replacement ...

Page 4: ...t pre lube design Excessive dirt oil should be periodically removed 4 Make sure oil is draining easily through drain pipe FIG 5 CHANGING FILTERS CAUTION Always make sure that the unit is turned off before changing filters or servicing the unit 1 The OM 500 is equipped with a filter change light or an optional Magnehelic Gauge which indicates when a filter needs to be replaced If the differential p...

Page 5: ...wire Burned out motor Replace motor Unit runs slowly or Wired for wrong voltage or Check input voltage Inadequate capture velocity Improper rotation Check wiring diagram Dirty filters Service filters see Changing Filters section Obstruction in hose arm Reach into hood and assembly remove obstruction Pulleys set for static Adjust or change pulleys Vibration Loose mounting bolts Tighten bolts Foreig...

Page 6: ...OM 500 WIRING DIAGRAM 6 OM500 FIG 6 ...

Page 7: ...762 Motor 208 230 460 V 21 P2250 Optional Magnehelic Gauge 7 P2064 Belt Not Shown P2061 Oil Impinger 8 P1789 Motor Pulley Not Shown P2062 Oil Bag Filter 9 P1710 Blower Pulley Not Shown P2072 Optional Hepa Filter 10 34134 01 Front Access Panel Not Shown P2070 Optional Oil Bag Filter 11 P1429 Lamp 120 V used with Hepa Filter P1481 Lamp 220 V Not Shown P3001 Optional 2 Max Grid Panel Filter 12 P1428 ...

Page 8: ...NOTES AIR CLEANERS Products of Metal Fab Inc P O BOX 1138 WICHITA KS 67201 1998 Metal Fab Inc Form No L1142 11 02 7051 Litho in U S A 8 OM500 ...