Page 34
Operation
MSC7401 Miniature sensor controller for inductive sensors
5.4.6
Example D: Adjustment via 2-point Adjustment
D1
D2
D3
D4
Set the sensor parameters according to example A and connect the output signal according to
example B.
G
MENU
Press the
MENU
button for 3 seconds
,
if you are not yet in the menu.
G
R
G
Output situation: The sensor parameters are already set; depending on the approach, LED
D4
is
green or switched off.
G
G
Go to the menu
Adjustment, see Chap.
5.3.4
.
ENTER
Confirm by pressing the
ENTER
button.
G
G
G
G
G
R
Select
2-point adjustment
.
ENTER
Confirm by pressing the
ENTER
button.
G
G
R
Now move the measuring object to the desired position start of measuring range (X
1
).
Use the arrow buttons to set 2.00 V (U
1
).
ENTER
Confirm by pressing the
ENTER
button.
G
G
R
Now move the measuring object 6.000 mm towards
the end of the measuring range (X
2
).
Use the arrow buttons to set 10.000 V (U
2
).
ENTER
Confirm by pressing the
ENTER
button.
G
R
G
X
U1
2
X
1
2
U (10 V)
(2 V)
6 mm
Fig. 24 Example 2-point Adjustment