54
Micro Motion
®
Model 2200S Transmitters
Configuring Operational Parameters
Note the following:
•
If you use the display to disable access to the off-line menu, the off-line menu will disappear
as soon as you exit the menu system. If you want to re-enable access, you must use ProLink II
or the Communicator.
•
Scroll Rate is used to control the speed of scrolling when Auto Scroll is enabled. Scroll Rate
defines how long each display variable (see Section 5.2.3) will be shown on the display. The
time period is defined in seconds; e.g., if Scroll Rate is set to 10, each display variable will be
shown on the display for 10 seconds.
If you are using the Communicator or the display to configure the display functions, you must
enable Auto Scroll before you can configure Scroll Rate.
•
The Off-line Password prevents unauthorized users from gaining access to the off-line menu.
The password can contain up to four numbers.
If you are using the Communicator or the display to configure the display functions, you must
enable the Off-line Password before you can configure it.
•
The level of alarm information available from the display is controlled by the combination of
Auto Scroll and Alarm Menu, as shown in Table 5-3 and the example following the table.
Table 5-3
Alarm information available from the display
Auto Scroll
Alarm Menu
Display behavior
Enabled
Enabled
• Flashes ALM_F if an alarm with severity level of Fault is active.
• Flashes ALM_I if an alarm with severity level of Informational is active but no
Fault alarm is active.
• Takes no action for alarms with severity level of Ignore.
• Displays alarm codes for all active Fault and Informational alarms after
scrolling through display variables.
Disabled
• Flashes ALM_F if an alarm with severity level of Fault is active.
• Flashes ALM_I if an alarm with severity level of Informational is active but no
Fault alarm is active.
• Takes no action for alarms with severity level of Ignore.
• Operator has no access to detailed alarm information from the display.
Disabled
Enabled
• Flashes ALM_F if an alarm with severity level of Fault is active.
• Flashes ALM_I if an alarm with severity level of Informational is active but no
Fault alarm is active.
• Takes no action for alarms with severity level of Ignore.
• Operator can access list of active alarm codes:
- By using the alarm menu
- By manually scrolling to the alarm portion of the display list
Disabled
• Flashes ALM_F if an alarm with severity level of Fault is active.
• Flashes ALM_I if an alarm with severity level of Informational is active but no
Fault alarm is active.
• Takes no action for alarms with severity level of Ignore.
• Operator has no access to detailed alarm information from the display.
Summary of Contents for 2200S
Page 8: ...vi Micro Motion Model 2200S Transmitters ...
Page 12: ...4 Micro Motion Model 2200S Transmitters ...
Page 32: ...24 Micro Motion Model 2200S Transmitters ...
Page 38: ...30 Micro Motion Model 2200S Transmitters ...
Page 68: ...60 Micro Motion Model 2200S Transmitters ...
Page 92: ...84 Micro Motion Model 2200S Transmitters ...
Page 102: ...94 Micro Motion Model 2200S Transmitters ...
Page 110: ...102 Micro Motion Model 2200S Transmitters ...
Page 130: ...122 Micro Motion Model 2200S Transmitters ...
Page 134: ...126 Micro Motion Model 2200S Transmitters ...
Page 150: ...142 Micro Motion Model 2200S Transmitters ...
Page 156: ...148 Micro Motion Model 2200S Transmitters ...
Page 157: ......