background image

Configuration and Use Manual

23

Quick Start

Op
eratio

n

App

e

ndi

ces

Mai

n

tenan

c

e and

 T

roub

le

sh
oo
tin
g

Com

m

is

si

on
in

g

Figure 2-17

Display menu – Alarms

SEE ALARM

Scroll

and

Select

simultaneously

for 4 seconds

ACK ALL

(1)

Yes

EXIT

Select

No

Alarm code

Scroll

ACK

Yes

Select

No

Active/

unacknowledged 

alarms?

No

Yes

Select

NO ALARM

EXIT

Scroll

Scroll

Select

Scroll

Scroll

Select

(1) This screen is displayed only if the ACK ALL 

function is enabled (see Section 5.2.4) and there are 
unacknowledged alarms.

Summary of Contents for 2200S

Page 1: ...Configuration and Use Manual P N MMI 20012741 Rev A September 2008 Micro Motion Model 2200S Transmitters Configuration and Use Manual ...

Page 2: ... MVD Direct Connect are trademarks of Micro Motion Inc Boulder Colorado Micro Motion is a registered trade name of Micro Motion Inc Boulder Colorado The Micro Motion and Emerson logos are trademarks and service marks of Emerson Electric Co All other trademarks are property of their respective owners ...

Page 3: ...ew 25 3 2 Applying power 25 3 3 Setting up and making an administrative connection 26 3 4 Working with the mA output scale 26 3 4 1 Specifying the mA measurement point 26 3 4 2 Converting between mA output scales 27 3 5 Configuration tips and tricks 28 3 5 1 Write protection 28 3 5 2 Default values and ranges 28 3 5 3 Restoring factory configuration 28 3 6 Display and reporting options for process...

Page 4: ...measurement 50 4 10 2 Interaction with the Added Damping parameter 50 Chapter 5 Configuring Operational Parameters 51 5 1 Overview 51 5 2 Configuring the display 51 5 2 1 Update period 51 5 2 2 Display language 51 5 2 3 Display variables and display precision 52 5 2 4 Enabling and disabling display functions 53 5 3 Configuring fault handling 55 5 3 1 Status alarm severity 55 5 3 2 Last measured va...

Page 5: ...g status alarms 87 8 6 1 About status alarms 87 8 6 2 With the display 88 8 6 3 With ProLink II 89 8 6 4 With the Communicator 90 8 7 Using the totalizers and inventories 90 8 7 1 Viewing current totals for totalizers and inventories 90 8 7 2 Controlling totalizers and inventories 92 Chapter 9 Measurement Performance 95 9 1 Overview 95 9 2 Meter validation and calibration 95 9 2 1 Meter validation...

Page 6: ... 10 23 1 Obtaining the test points 116 10 23 2 Drive gain problems 116 10 23 3 Low pickoff voltage 117 10 24 Checking sensor circuitry 117 Appendix A Default Values and Ranges 123 A 1 Overview 123 A 2 Most frequently used defaults and ranges 123 Appendix B Flowmeter Installation Types and Components 127 B 1 Overview 127 B 2 Transmitter components 127 B 3 Terminal diagrams 128 Appendix C Model 2200...

Page 7: ... 139 E 1 Overview 139 E 2 Communicator device description 139 E 3 Connecting to a transmitter 140 E 3 1 Connecting to HART clips 140 E 3 2 Connecting to a multidrop network 141 E 4 Using the Communicator with the Model 2200S 141 E 5 Communicator safety messages and notes 141 Index 143 ...

Page 8: ...vi Micro Motion Model 2200S Transmitters ...

Page 9: ...ganized into four sections as described in Table 1 1 Table 1 1 Manual organization Section Chapters Audience Description Commissioning 2 Person responsible for process design and device configuration Person responsible for device testing and commissioning Quick start tools for device commissioning 3 through 7 Detailed information for all parameters that can be configured Procedures for testing dev...

Page 10: ... Note Some configuration and administrative procedures can also be performed via the display menus However for complete access to transmitter functions Micro Motion recommends setting up and using an administrative connection Basic information on using ProLink II and connecting ProLink II to your transmitter is provided in Appendix D For more information see the ProLink II manual available on the ...

Page 11: ...ations phone 65 6777 8211 Singapore In Europe In the U K phone 0870 240 1978 toll free In other locations phone 31 0 318 495 555 The Netherlands Customers outside the U S A can also email Micro Motion customer service at International MMISupport EmersonProcess com Table 1 3 Flowmeter documentation resources Topic Document Sensor installation Sensor documentation Transmitter installation Micro Moti...

Page 12: ...4 Micro Motion Model 2200S Transmitters ...

Page 13: ...3 Menu flowcharts For the Communicator see Section 2 4 1 For ProLink II see Section 2 4 2 For the display see Section 2 4 3 If you need more help On using the display ProLink II or the Communicator see Appendix C D or E On general startup and configuration topics see Chapter 3 On configuration parameters see Chapters 4 through 6 On testing and final commissioning procedures see Chapter 7 2 2 Confi...

Page 14: ...igure mass flow measurement Configure volume flow meaurement Configure density measurement Done Configure temperature measurement Characterize the flowmeter Volume flow type Liquid Gas Define gas properties Configure display parameters Configure fault handling parameters Configure sensor parameters Configure device parameters Configure the mA output Configure digital communications Set up administ...

Page 15: ...__________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ Flow parameters Flow direction Forward Reverse Absolute Value Bidirectional Negate Forward Negate Absolute Value Flow damping Default 0 8 sec Other _...

Page 16: ..._____________________ ______________________ ______________________ ______________________ ______________________ ______________________ ______________________ ______________________ ______________________ Auto scroll Enabled Disabled Scroll rate Default 10 sec Other _______________________________________ Off line menu Enabled Disabled Off line password Enabled Disabled ______________________ Ala...

Page 17: ...__________ Date ______________________________________________ Chapter 6 mA output Scale at DCS 12 20 mA installation does not include adapter barrier 4 20 mA installation includes adapter barrier Primary variable PV Mass flow Volume flow GSV flow Temperature Density Drive gain LRV ______________________________________________ URV ______________________________________________ AO cutoff Default 0...

Page 18: ... flowcharts are based on Transmitter software v1 0 ProLink II v2 8 Field Communicator device description Micro Motion 2200S Analog dev rev 1 DD rev 1 Menus may vary slightly for different versions of these components Digital communications Fault action Upscale Downscale Internal zero Not a Number Flow to zero None Fault value __________ Fault value __________ Loop current mode Enabled Disabled Bur...

Page 19: ...ompensation Installed options Data Logging 1 Load from Xmtr to File Save to Xmtr from File License Connect to Device Connect to Fork Device Disconnect View Connection Commissioning Wizard Options ProLink II Language Error Log On Tools Plug ins ProLink Configuration Output Levels Process Variables Status Alarm Log Diagnostic Information Calibration Test Totalizer Control 1 For information about usi...

Page 20: ...mA measurement point AO fault action AO fault level level shifted AO fault level from transmitter Last measured value timeout ProLink Configuration Additional options Device Tag Date Descriptor Message Sensor type Transmitter serial number Floating pt ordering Add comm resp delay Digital comm settings Fault setting HART address Loop current mode HART device ID Burst setup Enable burst Burst cmd Bu...

Page 21: ...Base gas vol time 2 Gas vol flow conv fact 2 Gas vol flow text 2 Gas vol total text 2 Sensor Simulation Enable simulation mode Mass flow Wave form Fixed value Period Minimum Maximum Density Wave form Fixed value Period Minimum Maximum Temperature Wave form Fixed value Period Minimum Maximum 1 Displayed only if Vol Flow Type is set to Liquid Volume 2 Displayed only if Vol Flow Type is set to Standa...

Page 22: ...ead severity 3 Review severity all 4 Acknowledge selected alarm 5 Alarm event log 6 Refresh alarm event log Trim analog out 1 Scaled AO1 trim Test points 1 Status words 2 LPO 3 RPO 4 Tube 5 Drive 6 Board temperature 7 Live zero flow 8 Meter temp T Series 9 Input voltage Actual target amplitude Average sensor temp Min sensor temp Max sensor temp Min electronics temp Average electronics temp Wire RT...

Page 23: ...mperature 4 Pressure 1 Mass flow unit 2 Mass flow cutoff 3 Spcl mass units 4 Vol flow unit 5 Vol flow cutoff 6 Spcl vol units 7 Flo direction 8 Flo damp 1 1 Density unit 2 Density damp 3 Density cutoff 4 Slug low limit 5 Slug high limit 6 Slug duration 1 Temp unit 2 Temp damp 1 Pressure unit 2 3 4 Config outputs 1 Channel setup 2 HART output 3 Modbus data 4 Fault timeout 5 Comm fault indicator 1 A...

Page 24: ...n s Display setup 1 Enable disable 2 Display variables 3 Display precision 1 Display total reset 2 Display total start stop 3 Display auto scroll 4 Display offline menu 5 Display alarm menu 6 Display ACK All 7 Display offline password 8 Offline password 1 8 9 Update period 2 1 5 Setup simulation mode 1 Enable disable 2 Simulate mass flow 3 Simulate temperature 4 Simulate density 1 Displayed only i...

Page 25: ...display RESET YES Mass total Volume total Yes No EXIT Yes No Scroll Scroll Scroll Select Scroll Scroll Scroll Scroll Select Select Select 1 The transmitter must be configured to allow resetting totalizers from the display See Section 5 2 4 2 The transmitter must be configured to allow starting and stopping totalizers from the display See Section 5 2 4 Scroll and Select simultaneously for 4 seconds...

Page 26: ... Model 2200S Transmitters Quick Start Figure 2 12 Display menu Maintenance Version information Scroll and Select simultaneously for 4 seconds VER Yes Version info Scroll Select Scroll EXIT OFF LINE MAINT Select Scroll ...

Page 27: ...tors OFF LINE MAINT Scroll and Select simultaneously for 4 seconds Scroll Select Select Scroll CONFG MASS UNITS VOL 1 DENS TEMP Select Scroll Scroll Scroll Scroll PRESS AO 12 mA 20 mA Select Scroll Scroll EXIT Scroll SRC Scroll Scroll EXIT MASS MTR F VOL Select Scroll Scroll DENS EXIT Scroll Scroll Additional options 1 Either Vol or GSV is displayed depending on Volume Flow Type ...

Page 28: ...l AUTO SCRLL 2 Scroll OFFLINE PASSW 3 Scroll DISPLAY RATE DISPLAY LANG Scroll Scroll LOCK Scroll Scroll 1 If you disable access to the offline menu the offline menu will disappear as soon as you exit To re enable access you must use ProLink II or the Communicator 2 If Auto Scroll is enabled a Scroll Rate screen is displayed immediately after the Auto Scroll screen 3 If Offline Password is enabled ...

Page 29: ...e 2 15 Display menu Simulation loop testing Scroll and Select simultaneously for 4 seconds Yes Scroll Select SET MAO Scroll Select SET 16 mA Yes SET 20 mA Select 1 Yes Select 1 SET 12 mA Yes Select 1 EXIT Scroll Select 2 Scroll Select 2 Select 2 OFF LINE MAINT Select Scroll SIM 1 Fixes the output 2 Unfixes the output ...

Page 30: ...neously for 4 seconds Scroll Select Select CAL ZERO Troubleshoot ZERO YES CAL PASS CAL FAIL RESTORE ZERO RESTORE ZERO YES Current zero display Factory zero display Select Select Yes No EXIT Scroll Select Scroll Scroll Scroll Yes Select No Scroll ZERO Select Scroll RESTORE ZERO Scroll Select RESTORE EXIT Select Scroll Scroll ...

Page 31: ...s SEE ALARM Scroll and Select simultaneously for 4 seconds ACK ALL 1 Yes EXIT Select No Alarm code Scroll ACK Yes Select No Active unacknowledged alarms No Yes Select NO ALARM EXIT Scroll Scroll Select Scroll Scroll Select 1 This screen is displayed only if the ACK ALL function is enabled see Section 5 2 4 and there are unacknowledged alarms ...

Page 32: ...24 Micro Motion Model 2200S Transmitters ...

Page 33: ...place before applying power Operating the flowmeter without covers in place creates electrical hazards that can cause death injury or property damage 2 Apply power to the mA output wiring The flowmeter will automatically perform diagnostic routines When the flowmeter has completed its power up sequence if the default settings are in effect The display will show the current mass flow rate and measu...

Page 34: ...ommunicate with the transmitter To set the software tag Using the Communicator select Detailed Setup Device Information Tag Using ProLink II click ProLink Configuration Device 4 Disconnect the startup connection and reconnect using the new parameters 3 4 Working with the mA output scale If the Micro Motion adapter barrier is installed the mA signal received by the host is scaled from 4 20 mA If th...

Page 35: ...dapter barrier use 12 20 mA If the mA measurement device is between the adapter barrier and the host use 4 20 mA If you don t know how to set the mA measurement point specify Don t Know The Communicator and ProLink II will display data for both output scales Figure 3 1 mA measurement point options 3 4 2 Converting between mA output scales Equations for converting between mA output scales are shown...

Page 36: ...e most commonly used parameters are provided in Appendix A 3 5 3 Restoring factory configuration If you are using ProLink II or the Communicator you can restore the factory configuration to return to a known state To do this Using ProLink II click ProLink Configuration Device then click Restore Factory Configuration Using the Communicator select Diag Service Perform Diagnostic Action Restore Facto...

Page 37: ...efer to this list as you plan the transmitter configuration Table 3 2 Process variables and display reporting query options Process variable Display reporting and query options Display mA output HART PV HART SV HART TV HART QV Mass flow Volume flow 1 1 Volume and GSV process variables are mutually exclusive GSV flow 1 Temperature process Density Drive gain Mass total Volume total 1 GSV total 1 Mas...

Page 38: ...30 Micro Motion Model 2200S Transmitters ...

Page 39: ...ake an administrative connection to the transmitter and ensure that you are complying with all applicable safety requirements 4 2 Characterizing the flowmeter Characterizing the flowmeter adjusts the transmitter to compensate for the unique traits of the sensor it is paired with The characterization parameters or calibration parameters describe the sensor s sensitivity to flow density and temperat...

Page 40: ...on parameter controls how the transmitter reports flow rate and how flow is added to or subtracted from the totalizers under conditions of forward flow reverse flow or zero flow Forward positive flow moves in the direction of the arrow on the sensor Reverse negative flow moves in the direction opposite of the arrow on the sensor Table 4 1 Characterization parameters Parameter Description Sample se...

Page 41: ...4 mA For a discussion of these figures see the examples following the figures For the effect of Flow Direction on totalizers and the flow values reported via digital communications see Table 4 2 Figure 4 1 Effect of flow direction on mA output LRV 0 Reverse flow 1 20 16 12 x 0 20 16 12 x x 0 mA output configuration URV x LRV 0 To set the LRV and URV see Section 6 2 2 Forward flow 2 Zero flow Rever...

Page 42: ...forward flow if the absolute value of the flow rate equals or exceeds 100 g s the mA output will be proportional to the flow rate up to 20 5 mA and will be level at 20 5 mA at higher flow rates Reverse flow 1 mA output 20 16 12 x x 0 20 16 x x 0 mA output configuration URV x LRV x x 0 To set the LRV and URV see Section 6 2 2 Forward flow 2 Zero flow Reverse flow 1 Forward flow 2 Zero flow Flow dir...

Page 43: ...rward Only mA output LRV 100 g s URV 100 g s See the first graph in Figure 4 2 As a result Under conditions of zero flow the mA output is 12 mA before respanning Under conditions of forward flow up to a flow rate of 100 g s the mA output of the transmitter varies between 12 mA and 20 mA in proportion to the absolute value of the flow rate Under conditions of forward flow if the absolute value of t...

Page 44: ...ct of flow direction on totalizers and digital communications Flow direction value Forward flow Flow totals Flow values via digital comm Forward only Increase Positive Reverse only No change Positive Bidirectional Increase Positive Absolute value Increase Positive 1 1 Refer to the digital communications status bits for an indication of whether flow is positive or negative Negate Forward No change ...

Page 45: ...ng ProLink II click ProLink Configuration Flow Using the display see Figure 2 13 Table 4 3 Mass flow measurement units Mass flow unit Unit description Display Communicator ProLink II G S g s g s Grams per second G MIN g min g min Grams per minute G H g h g hr Grams per hour KG S kg s kg s Kilograms per second KG MIN kg min kg min Kilograms per minute KG H kg h kg hr Kilograms per hour KG D kg d kg...

Page 46: ...lect Detailed Setup Config Fld Dev Var Flow Using ProLink II click ProLink Configuration Flow Note You cannot configure the mass flow cutoff with the display 4 4 3 Defining a special unit for mass flow To define a special unit for mass flow 1 Navigate to the special units menu If you are using the Communicator select Detailed Setup Config Fld Dev Var Flow Spcl mass units If you are using ProLink I...

Page 47: ...r a gas Your choice here controls the volume measurement units that are available If you specify Gas Standard Volume GSV you must describe the properties of your gas see Section 4 6 Configuration To configure Volume Flow Type Using the Communicator select Detailed Setup Config Fld Dev Var Flow Using ProLink II click ProLink Configuration Flow Using the display see Figure 2 14 4 5 2 Volume flow mea...

Page 48: ...nute USGPH gal h US gal hr U S gallons per hour USGPD gal d US gal d U S gallons per day MILG D MMgal d mil US gal day Million U S gallons per day L S L s l sec Liters per second L MIN L min l min Liters per minute L H L h l hr Liters per hour MILL d ML d mil l day Million liters per day UKGPS Impgal s Imp gal sec Imperial gallons per second UKGPM Impgal min Imp gal min Imperial gallons per minute...

Page 49: ...ailable Nm3 min Normal cubic meters per minute NM3 H Not available Nm3 hr Normal cubic meters per hour NM3 D Not available Nm3 day Normal cubic meters per day NLPS Not available NLPS Normal liter per second NLPM Not available NLPM Normal liter per minute NLPH Not available NLPH Normal liter per hour NLPD Not available NLPD Normal liter per day SCFS Not available SCFS Standard cubic feet per second...

Page 50: ... values as required Note The Gas Wizard displays density temperature and pressure in the configured units If required you can configure the transmitter to use different units 4 6 1 Volume or GSV flow cutoff If the volume or GSV flow measurement drops below the configured volume or GSV flow cutoff the transmitter will report a value of 0 for volume flow or GSV flow Note the following If Volume Flow...

Page 51: ...pecify the existing time unit that the special unit will be based on 4 Calculate and specify the volume flow or GSV conversion factor This value is used to calculate the special unit from the base mass unit and the base time unit Use the following equations 5 Assign a name to the new special unit for volume or GSV flow 6 Assign a name to the unit to be used for the associated volume or GSV totaliz...

Page 52: ...Detailed Setup Config Fld Dev Var Density Using ProLink II click ProLink Configuration Density Using the display see Figure 2 13 4 7 2 Density cutoff If the density measurement drops below the configured density cutoff the transmitter will report a value of 0 for density Table 4 6 Density measurement units Density unit Unit description Display Communicator ProLink II SGU SGU SGU Specific gravity u...

Page 53: ... ProLink Configuration Density Note You cannot configure density damping with the display 4 7 4 Slug flow parameters Slugs gas in a liquid process or liquid in a gas process occasionally appear in some applications The presence of slugs can significantly affect the process density reading The slug flow parameters can help the transmitter suppress extreme changes in process variables and can also b...

Page 54: ...other unit has been configured for density Slug flow duration is entered in seconds Note Raising the low slug flow limit or lowering the high slug flow limit will increase the possibility of slug flow conditions Conversely lowering the low slug flow limit or raising the high slug flow limit will decrease the possibility of slug flow conditions Note If slug flow duration is set to 0 the mass flow r...

Page 55: ...sity sensitivity due to process pressure change away from calibration pressure Note Pressure compensation is optional Perform this procedure only if required by your application The Model 2200S transmitter supports only static pressure compensation i e the external pressure is a known static value 4 9 1 Pressure correction factors When configuring pressure compensation you must provide the flow ca...

Page 56: ...on procedure To enable and configure pressure compensation With the Communicator see Figure 4 3 With ProLink II see Figure 4 4 Note You cannot configure pressure compensation with the display Figure 4 3 Configuring pressure compensation with the Communicator Enter Flow factr Configure pressure compensation Enter Dens factr Enter Flowcal pressure Enter Static Pressure 6 Pressure Comp 2 Config field...

Page 57: ...ee Sections 4 3 2 4 7 3 and 4 8 2 When you specify a new damping value it is automatically rounded down to the nearest valid damping value Valid damping values are listed in Table 4 8 Note For gas applications Micro Motion recommends a minimum flow damping value of 2 56 Before setting the damping values review the following sections for information on how the damping values interact with other tra...

Page 58: ...efore only damping applied to mass flow will affect gas standard volume measurement Be sure to set damping values accordingly 4 10 2 Interaction with the Added Damping parameter The mA output has a damping parameter called Added Damping If damping is set to non zero value for flow density or temperature the same process variable is assigned to the mA output and Added Damping is also set to a non z...

Page 59: ...ith all applicable safety requirements 5 2 Configuring the display You can configure a variety of parameters to control display behavior and operator actions at the display 5 2 1 Update period The Update Period parameter controls how often the display is refreshed with current data The default is 200 milliseconds the range is 100 milliseconds to 10 000 milliseconds 10 seconds Configuration To conf...

Page 60: ...able of displaying special measurement units If you have defined a special measurement unit it will be listed for selection Table 5 1 shows an example of a display variable configuration Notice that you can repeat variables and you can also specify None for any display variable except Display Var 1 For information on how the display variables will appear on the display see Appendix C Configuration...

Page 61: ...s using the display buttons Totalizer Reset Yes Operators can reset the mass and volume totalizers using the display buttons Operators cannot reset the mass and volume totalizers using the display buttons Auto Scroll No The display automatically scrolls through the list of display variables at a configurable rate If Alarm Menu is enabled active alarms 1 are listed after the display variables See t...

Page 62: ...ble Table 5 3 Alarm information available from the display Auto Scroll Alarm Menu Display behavior Enabled Enabled Flashes ALM_F if an alarm with severity level of Fault is active Flashes ALM_I if an alarm with severity level of Informational is active but no Fault alarm is active Takes no action for alarms with severity level of Ignore Displays alarm codes for all active Fault and Informational a...

Page 63: ...gital communications fault action is always performed immediately 5 3 1 Status alarm severity Status alarms are classified into three levels of severity The severity level controls transmitter behavior when the alarm condition occurs See Table 5 4 Example Case 1 Operators do not need to know which alarms are active There are no special requirements for configuring Auto Scroll and Alarm Menu The di...

Page 64: ...M_I flashes on the display and the alarm is posted to the active alarm log but fault actions are not performed Ignore If this condition occurs the alarm status flags are set but no entry is added to the active alarm log the display does not show an alarm and no fault actions are performed Table 5 5 Status alarms and severity levels Alarm code Communicator message Default severity Configurable Affe...

Page 65: ...unication Failure A030 Hardware Software Incompatible Fault No No Incorrect Board Type A031 Undefined Fault No No Low Power A033 Tube Not Full Fault No Yes Tube Not Full A100 Primary mA Output Saturated Info Yes 1 No Primary mA Output Saturated A101 Primary mA Output Fixed Info Yes 1 No Primary mA Output Fixed A102 Drive Over Range Info Yes No Drive Overrange A104 Calibration In Progress Info Yes ...

Page 66: ...formed immediately Note For all faults the digital communications fault action is performed immediately For information on which faults are affected by LMV Timeout see Table 5 5 Configuration To configure LMV Timeout Using the Communicator select Detailed Setup Config Outputs Channel Setup AO Setup AO1 Fault Setup Using ProLink II click ProLink Configuration Analog Output Note You cannot configure...

Page 67: ...igure device parameters Using the Communicator select Detailed Setup Device Information Using ProLink II click ProLink Configuration Device Note You cannot configure device parameters with the display If you are entering a date With ProLink II use the left and right arrows at the top of the calendar to select the year and month then click on a date With a Communicator enter a value in the form mm ...

Page 68: ...60 Micro Motion Model 2200S Transmitters ...

Page 69: ... how the process variable is reported Table 6 1 lists the parameters that must be set for the mA output and shows the names used for each parameter by the display the Communicator and ProLink II Note If you use the display you can configure only the process variable LRV and URV For details on mA output parameters see Sections 6 2 1 through 6 2 4 Table 6 1 mA output configuration parameters Paramet...

Page 70: ... represented by a transmitter output of 12 mA The upper range value URV the value of the process variable that will be represented by a transmitter output of 20 mA Note If the Micro Motion adapter barrier is installed the LRV will be represented by a transmitter output of 12 mA and an adapter barrier output of 4 mA The URV is not affected Note the following The URV can be set below the LRV for exa...

Page 71: ...as been assigned to the mA output the AO Cutoff menu option is not available Note For most applications the default AO cutoff is used Contact Micro Motion customer support before changing the AO cutoff Multiple cutoffs Cutoffs can also be configured for the mass flow and volume flow process variables see Sections 4 4 2 and 4 6 1 If mass flow or volume flow has been assigned to the mA output a non ...

Page 72: ...more erratic because the output changes more quickly The Added Damping parameter specifies damping that will be applied to the mA output It affects the measurement of the process variable assigned to the mA output Note For most applications the default added damping value is used Contact Micro Motion customer support before changing the Added Damping parameter Multiple damping parameters Damping c...

Page 73: ...configurable Table 6 4 mA output fault actions and values Fault action Output scale Fault output value Upscale N A 21 24 mA user configurable default 22 mA Downscale 12 20 mA 10 5 11 8 mA user configurable default 11 0 mA 4 20 mA 1 0 3 6 mA user configurable default 2 0 mA Internal zero N A Goes to the mA output level associated with a process variable value of 0 zero as determined by URV and LRV ...

Page 74: ...tion by changing LMV Timeout See Section 5 3 2 Fault indication with the mA output Depending on your process and control system you may be able to use the mA fault action as a fault indicator If you choose to do this be sure that your control system recognizes the configured fault value as a fault If mA Fault Action is set to None make sure that a fault detection method is in place e g checking st...

Page 75: ...rameter is enabled the mA output will report process data as configured Table 6 5 Digital communications fault actions and values Fault Action code Fault output value Communicator ProLink II Upscale Upscale Process variables indicate the value is greater than the upper sensor limit Totalizers stop incrementing Downscale Downscale Process variables indicate the value is less than the lower sensor l...

Page 76: ...oop Current Mode with the display or the Communicator 6 3 3 PV SV TV and QV assignments In the transmitter four variables are defined for HART communications the PV primary variable the SV secondary variable the TV tertiary variable and the QV quaternary variable A process variable such as mass flow is assigned to each HART variable The values of the assigned process variables can be reported or r...

Page 77: ...dem as required by ProLink II may be very slow or the HART connection may fail completely If either of these occurs disable burst mode use a communications tool that does not require a HART modem i e the Communicator try a HART modem from a different vendor or try a USB HART modem Ensure that RTS line control is managed by the modem Configuration To configure burst mode 1 Navigate to the correct m...

Page 78: ... burst e g 25 11 0 mA 1 1 If the Micro Motion adapter barrier is installed the mA value will be converted to the 4 20 mA output scale at the adapter barrier Dynamic vars PV current 2 2 This burst mode setting is typically used with the HART Tri Loop signal converter See the Tri Loop manual for additional information Process variables current The transmitter sends PV SV TV and quaternary variable Q...

Page 79: ...as zeroed at the factory and should not require a field zero However you may wish to perform a field zero to meet local requirements or to confirm the factory zero When you zero the flowmeter you may need to adjust the zero time parameter Zero time is the amount of time the transmitter takes to determine its zero flow reference point The default zero time is 20 seconds A long zero time may produce...

Page 80: ... procedure 1 Apply power to the flowmeter Allow the flowmeter to warm up for approximately 20 minutes 2 Run the process fluid through the sensor until the sensor temperature reaches the normal process operating temperature 3 Close the shutoff valve downstream from the sensor 4 Ensure that the sensor is completely filled with fluid 5 Ensure that the process flow has completely stopped CAUTION Ensur...

Page 81: ...eshooting Commissioning Figure 7 1 Display Flowmeter zero procedure OFF LINE MAINT Scroll and Select simultaneously for 4 seconds Scroll Select Select ZERO ZERO YES CAL PASS CAL FAIL EXIT Scroll Scroll Select ZERO Troubleshoot Select Note For a complete presentation of the Zero menu structure see Figure 2 16 ...

Page 82: ...required Perform auto zero Auto Zero Failed Auto Zero Complete OK 1 Auto zero Calibration in Progress message OK On Line Menu 3 Diag Service 3 Calibration Troubleshoot Modify zero time if required Calibration Failure LED Calibration in Progress LED turns red Green Troubleshoot Red Perform Auto Zero Done ProLink Calibration Zero Calibration Wait until Calibration in Progress LED turns green ...

Page 83: ...ss control while you are performing the loop test If you are using ProLink II or the Communicator enter the fixed value in the scale that you specified for the mA measurement point If you specified Don t Know If you are using ProLink II enter the desired value in one scale and the tool will display the equivalent value in the other scale If you are using the Communicator you must specify the mA me...

Page 84: ...eously for 4 seconds OFFLINE SIM Yes Select SET MAO Scroll Select SET 16 mA Yes SET 20 mA Select Select Scroll No Troubleshoot Correct at receiving device Yes Yes Select Select Scroll No Troubleshoot Correct at receiving device Yes SET 12 mA Yes Select No Troubleshoot Correct at receiving device Yes Select EXIT OFFLINE MAINT Scroll Scroll ...

Page 85: ...aintenance and Troubleshooting Commissioning Figure 7 5 Communicator Loop test procedure 1 Fix Analog Out 1 Set mA measurement point Correct Loop test successful END to unfix Check output wiring Troubleshoot receiving device Yes No 4 mA 20 mA Other On Line Menu 3 Diag Service 2 Loop test ...

Page 86: ...ion adapter barrier is installed the mA output trim procedure can be extended to include additional trimming and calibration See Section 7 4 2 You must trim the mA output at both the 12 mA and 20 mA points to ensure appropriate compensation across the entire output range 7 4 1 Basic mA output trim To trim the output Using the Communicator see Figure 7 7 Using ProLink II see Figure 7 8 Additionally...

Page 87: ...cale If you are using the Communicator you must specify the mA measurement point before you can continue Any trimming performed on the output should not exceed 200 microamps If more trimming is required contact Micro Motion customer support If you are using the Communicator the receiving device value can contain up to two decimal places Figure 7 7 Communicator mA output trim procedure Read mA outp...

Page 88: ...ving device Read mA output at receiving device Equal Enter receiving device value in Enter Meas Read mA output at receiving device Read mA output at receiving device Equal Enter receiving device value in Enter Meas 4 12 mA trim 20 mA trim Yes No Yes Next Next Next ProLink Calibration Milliamp 1 Trim Back No Back Finish Set mA measurement point ...

Page 89: ...oint 12 20 mA 2 At the transmitter fix the mA output to 12 mA then check the mA reading at the host 3 At the transmitter fix the mA output to 20 mA then check the mA reading at the host 4 If the mA readings at the host do not meet accuracy requirements If you have an third party barrier troubleshoot the barrier installation and wiring If you have the Micro Motion adapter barrier calibrate the adap...

Page 90: ...does not change any diagnostic values CAUTION Be sure that your process is prepared to handle the consequences of your simulation setup To set up sensor simulation follow the steps below 1 If you are using The Communicator refer to Figure 2 9 ProLink II refer to Figure 2 4 2 Enable sensor simulation mode 3 For mass flow a Specify the type of simulation you want fixed value triangular wave or sine ...

Page 91: ...protect the configuration using ProLink II 1 Click ProLink Configuration Device 2 Enable write protection To write protect the configuration using the Communicator 1 Select Diag Service Perform Diagnostic Action 2 Select Enable Write Protect To write protect the configuration using the display 1 Enter the display menu system 2 Enter the off line maintenance menu 3 Select the Config menu and scroll...

Page 92: ...84 Micro Motion Model 2200S Transmitters ...

Page 93: ...s chapter Note All Communicator key sequences in this section assume that you are starting from the Online menu See Appendix E for more information 8 2 Warm up delay If you have just powered up the flowmeter the transmitter may not be warmed up sufficiently and may exhibit minor instability or inaccuracy If you observe this wait approximately ten minutes If the condition does not disappear follow ...

Page 94: ...r of seconds specified for Scroll Rate Whether Auto Scroll is enabled or not the operator can manually scroll through the configured display variables by pressing Scroll If more than one line is required to describe the display variable the Units of measure line alternates between the measurement unit and the additional description For example if the LCD is displaying a mass inventory value the Un...

Page 95: ...aphics types are not implemented The Communicator provides several functions for manipulating the graph such as panning and zooming These functions are implemented See the Communicator documentation for additional instructions on using the graphics function 8 6 Viewing and acknowledging status alarms Specific process or flowmeter conditions cause status alarms Note For detailed information on stat...

Page 96: ... You can use the process variable display to determine if an unidentified Fault or Informational alarm is active No alarm codes are provided You can view the list of active Fault and Informational alarms from the process variable display This list identifies alarms by alarm code You can use the display alarm menu to view active and unacknowledged Fault and Informational alarms and you can acknowle...

Page 97: ...icates inactive but unacknowledged and a red LED indicates active Alarms are organized into two categories High Priority and Low Priority You can view and acknowledge alarms from the Alarm Log window Note The location of alarms in the Status window or the Alarm Log window is not affected by the configured alarm severity Alarms are predefined as Critical Informational or Operational or as High Prio...

Page 98: ...ontains The alarm code The alarm status e g cleared but unacknowledged The timestamp which is the number of seconds that this alarm has been active while the transmitter has been powered on Note The timestamp value is not reset during a transmitter power cycle To reset this value you must perform a master reset or use a Modbus command Contact Micro Motion customer support To view records in the al...

Page 99: ...entory begins to alternate with the units of measure For gas volume inventory the word GSVI Gas Standard Volume Inventory begins to alternate with the units of measure See Figure 8 1 Read the current value from the top line of the display Figure 8 1 Totalizer values on display With ProLink II To view current totals for the totalizers and inventories with ProLink II 1 Click ProLink 2 Select Process...

Page 100: ...This feature may be enabled or disabled See Section 5 2 4 Scroll until a totalizer value appears the word TOTAL appears in the lower left corner of the display It does not matter whether the total is mass or volume Select Scroll until STOP appears beneath the current totalizer value Select YES alternates with STOP Select all totalizers and inventories stop Scroll to EXIT Start all totalizers and i...

Page 101: ...ventories Click Start Reset mass totalizer Click Reset Mass Total Reset volume totalizer Click Reset Volume Total Simultaneously reset all totalizers Click Reset Simultaneously reset all inventories 1 1 If enabled in the ProLink II Preferences window Click Reset Inventories Reset mass inventory only 1 Click Reset Mass Inventory Reset volume liquid or gas inventory only 1 Click Reset Volume Invento...

Page 102: ...94 Micro Motion Model 2200S Transmitters ...

Page 103: ...d in Sections 9 2 2 and 9 2 3 Before performing any of these procedures review these sections to ensure that you will be performing the appropriate procedure for your purposes 9 2 1 Meter validation and meter factors Meter validation compares a measurement value reported by the transmitter with an external measurement standard Meter validation requires one data point Note For meter validation to b...

Page 104: ...to correct measurement error 9 2 3 Comparison and recommendations When choosing between meter validation and calibration consider the following factors Process interruption Meter validation does not interrupt the process Calibration requires process down time In addition density and temperature calibration require replacing the process fluid with low density and high density fluids or low temperat...

Page 105: ...or note that proving volume in the field may be expensive and the procedure may be hazardous for some process fluids Therefore because volume is inversely proportional to density an alternative to direct sampling and measurement is to calculate the volume flow meter factor from the density meter factor This method provides partial correction by adjusting for any portion of the total offset that is...

Page 106: ...t be at the lowest rate allowed by your application This is usually accomplished by closing the shutoff valve downstream from the sensor then filling the sensor with the appropriate fluid Density calibration fluids D1 and D2 density calibration require a D1 low density fluid and a D2 high density fluid You may use air and water 9 4 2 Density calibration procedures To perform a D1 and D2 density ca...

Page 107: ...message Calibration in Progress message D1 calibration Close shutoff valve downstream from sensor Fill sensor with D1 fluid Fill sensor with D2 fluid D2 calibration OK 1 Dens Pt 1 Perform Cal OK Home Enter density of D2 fluid Density Calibration Complete message Calibration in Progress message OK 2 Dens Pt 2 Perform Cal OK Home Done On Line Menu 3 Diag Service 3 Calibration 2 Density cal 3 Diag Se...

Page 108: ...ibration in Progress light turns red D1 calibration Close shutoff valve downstream from sensor Fill sensor with D1 fluid Fill sensor with D2 fluid Close Enter density of D2 fluid Calibration in Progress light turns green Calibration in Progress light turns red D2 calibration Close Done Do Cal Do Cal ProLink Menu Calibration Density cal Point 1 ProLink Menu Calibration Density cal Point 2 ...

Page 109: ...known values You can calibrate for temperature with ProLink II software See Figure 9 3 Figure 9 3 Temperature calibration ProLink II Enter temperature of low temperature fluid Temperature Offset calibration Do Cal Wait until sensor achieves thermal equilibrium Fill sensor with low temperature fluid Calibration in Progress light turns green Calibration in Progress light turns red Close Enter temper...

Page 110: ...102 Micro Motion Model 2200S Transmitters ...

Page 111: ...mation Note All Communicator key sequences in this section assume that you are starting from the Online menu See Appendix E for more information 10 2 Guide to troubleshooting topics Refer to Table 10 1 for a list of troubleshooting topics discussed in this chapter Table 10 1 Troubleshooting topics and locations Section Topic Section 10 4 Transmitter does not operate Section 10 5 Transmitter does n...

Page 112: ...es in Section 10 14 3 For communication using a communication device check the wiring and the communication device See Appendix D for ProLink II or Appendix E for the 375 Field Communicator If you can read data from the transmitter but cannot write data e g you cannot start stop or reset totalizers or change transmitter configuration check to see if the transmitter is write protected and disable w...

Page 113: ...fied in the transmitter installation manual Remove gas from the process fluid 10 8 Fault conditions If the mA output or digital communications is performing its fault action determine the exact nature of the fault by viewing the status alarms Once you have identified the status alarm s associated with the fault condition refer to Section 10 12 Some fault conditions can be corrected by cycling powe...

Page 114: ...tallation manual Constant mA output Non zero HART address Set HART address to 0 or enable the Loop Current Mode parameter See Section 10 19 Output is fixed in a test mode Exit output from test mode See Section 7 3 Zero calibration failure Cycle power Stop flow and rezero See Section 7 2 mA output consistently out of range Fault condition if fault indicator is set to upscale or downscale Check the ...

Page 115: ...service Contact Micro Motion E EPROM Checksum Error CP A002 RAM Test Error Core Processor ROM checksum error or a RAM location cannot be written to Cycle power to the flowmeter The flowmeter might need service Contact Micro Motion RAM Error CP A003 Sensor Not Responding No Tube Interrupt Continuity failure of drive circuit LPO or RPO or LPO RPO mismatch when driving Check for slug flow See Section...

Page 116: ...that there is no flow through the sensor then retry Cycle power to the flowmeter then retry If appropriate restore the factory zero to return the flowmeter to operation Zero Too Low A012 Excess Calibration Correction Zero too High See A10 Ensure that there is no flow through the sensor then retry Cycle power to the flowmeter then retry If appropriate restore the factory zero to return the flowmete...

Page 117: ...sting that sensor tubes are not vibrating Verify process Check for air in the flow tubes tubes not filled foreign material in tubes or coating in tubes Tube Not Full A100 Primary mA Output Saturated The calculated amount of current output is outside of the linear range See Section 10 18 Primary mA Output Saturated A101 Primary mA Output Fixed Non zero HART address configured or user has fixed the ...

Page 118: ...e 10 4 lists several possible problems and suggested remedies A106 Burst Mode Enabled Device is in HART burst mode No action required If desired reconfigure the alarm severity to Ignore see Section 5 3 1 Burst Mode Enabled AI or AO Simulate Active A107 Power Reset Occurred The transmitter has been restarted No action required If desired reconfigure the alarm severity to Ignore see Section 5 3 1 Po...

Page 119: ...lar 0 5 Hz tube frequency Erratic non zero flow rate when flow is steady Slug flow See Section 10 17 Damping value too low Check configuration See Section 4 10 Plugged flow tube Check drive gain and tube frequency Purge the flow tubes Excessive or erratic drive gain See Section 10 23 2 Output wiring problem Verify wiring between transmitter and receiving device See the installation manual for your...

Page 120: ...e changed Check for corrosion erosion or tube damage Temperature reading significantly different from process temperature RTD failure Check for alarm conditions and follow troubleshooting procedure for indicated alarm Temperature reading slightly different from process temperature Sensor leaking heat Insulate the sensor Unusually high density reading Plugged flow tube Check drive gain and tube fre...

Page 121: ...he active passive power configuration of the barrier matches the wiring If external power is being used verify the power supply to the barrier Test HART communications on both sides of the barrier and verify that the barrier is capable of passing HART communication signals 3 If you are connecting directly to the HART clips ensure that there is no loop resistance on these terminals If your HART net...

Page 122: ... barrier if applicable If an I S barrier or Micro Motion adapter barrier is installed test the signal between the transmitter and the barrier then between the barrier and the receiving device If required trim the mA output or calibrate the barrier Try a different receiving device Use sensor simulation to locate the problem See Section 10 11 10 17 Checking slug flow A slug flow alarm is posted when...

Page 123: ...e fault conditions To resolve this problem try the following Enable the Loop Current Mode parameter See Section 6 3 2 Set the HART address to 0 See Section 3 3 10 20 Checking the flow measurement configuration If the transmitter appears to be operating correctly but the flow data is unexpected Ensure that the transmitter is using the measurement unit that the remote device is expecting Check the a...

Page 124: ...r than a failed sensor You can diagnose sensor failure or overrange status alarms by checking the flowmeter test points The test points include left and right pickoff voltages drive gain and tube frequency These values describe the current operation of the sensor 10 23 1 Obtaining the test points You can obtain the test points with a Communicator or ProLink II With a Communicator To obtain the tes...

Page 125: ... sensor tubes are free to vibrate Possible problems include Pipe stress Check for pipe stress and eliminate if present Lateral tube shift due to hammer effect If this is a possibility contact Micro Motion Warped tubes caused by overpressurization If this is a possibility contact Micro Motion Incorrect sensor type configured Verify sensor type configuration then verify sensor characterization See S...

Page 126: ...captive user interface screws c Gently lift the user interface module disengaging it from the connector on the transmitter d Disconnect the I O wires from the I O terminals terminals 1 4 e Loosen the Warning flap screw raise the Warning flap and disconnect the power wires from the power terminals f Two captive screws 2 5 mm hex head hold the transmitter in the housing Loosen the screws and gently ...

Page 127: ...ransmitter to a different position In this test There should be no open circuits i e no infinite resistance readings Nominal resistance values vary 40 per 100 C However confirming an open or shorted circuit is more important than any slight deviation from the resistance values shown here The LPO and RPO circuit readings should be the same or very close 10 The readings across pin pairs should be st...

Page 128: ... pins except RTD and LLC RTD LLC RTD against all other pins except RTD and RTD Table 10 7 Nominal resistance ranges for flowmeter circuits Circuit Pin pairs Nominal resistance range 1 1 Actual resistance values depend on the sensor model and date of manufacture Contact Micro Motion for more detailed data Drive Drive and 8 1500 Ω Left pickoff Left pickoff and 16 1000 Ω Right pickoff Right pickoff a...

Page 129: ...tter housing and tighten the screws 3 Reconnect the I O wires 4 Reconnect the power wires lower the Warning flap and tighten the Warning flap screw 5 Plug the user interface module onto the transmitter There are four possible positions select the position that is most convenient 6 Tighten the user interface screws 7 Replace the user interface cover on the user interface module and tighten the scre...

Page 130: ...122 Micro Motion Model 2200S Transmitters ...

Page 131: ...e default values and ranges for the most frequently used transmitter settings Table A 1 Transmitter default values and ranges Type Setting Default Range Comments Flow Flow direction Forward Flow damping 0 64 sec 0 0 60 0 sec User entered value is corrected to nearest lower value in list of preset values For gas applications Micro Motion recommends a minimum value of 2 56 Mass flow units g s Mass f...

Page 132: ...entered value is corrected to nearest lower value in list of preset values Temperature units Deg C Temperature calibration factor 1 00000T0 0000 T Series sensor D3 0 00000 D4 0 00000 K3 0 00000 K4 0 00000 FTG 0 00000 FFQ 0 00000 DTG 0 00000 DFQ1 0 00000 DFQ2 0 00000 Special units Base mass unit g Base mass time sec Mass flow conversion factor 1 00000 Base volume unit L Base volume time sec Volume ...

Page 133: ...et when primary variable is reset AO cutoff 0 00000 g s AO added damping 0 00000 sec 0 440 seconds Fault action Downscale AO fault level downscale 2 0 mA 1 0 3 6 mA AO fault level upscale 22 mA 21 0 24 0 mA Last measured value timeout 0 00 sec Display Update period 200 milliseconds 100 10 000 milliseconds Variable 1 Mass flow rate Variable 2 Mass total Variable 3 Volume flow rate Variable 4 Volume...

Page 134: ...126 Micro Motion Model 2200S Transmitters ...

Page 135: ... transmitter installation manual B 2 Transmitter components The Model 2200S transmitter can be either integral mount or extended mount Figure B 1 shows an exploded view of the Model 2200S transmitter and its components integral mount Figure B 2 shows the extended mount option Figure B 1 Model 2200S transmitter Integral mount exploded view Sensor case Clamp Feedthrough Transmitter housing Transmitt...

Page 136: ...he transmitter s wiring terminals These terminals are used for both power supply and I O They are beneath the Warning flap The transmitter housing cover and the Warning flap screw must be removed to access the wiring terminals Figure B 3 Wiring terminals Conduit openings Clamping ring Sensor case Sensor case Transmitter housing cover Warning flap opened Terminal 2 Terminal 1 ...

Page 137: ...of the user interface see Section C 2 Removing and replacing the transmitter housing cover see Section C 3 Using the display see Section C 4 Codes and abbreviations used by the display see Section C 5 C 2 Identifying the components of the user interface The user interface of the Model 2200S transmitter is shown in Figure C 1 The transmitter housing cover has been removed Figure C 1 User interface ...

Page 138: ...rmation on reading alarm information from the display see Section 8 6 2 In general The Scroll button moves to the next item in the display menu The Select button selects the current item for use To use the buttons 1 Remove the transmitter housing cover as described in Section C 3 2 Press the button You will see the result of your action on the display There is no other confirmation C 4 1 Accessing...

Page 139: ... of the active digit 1 becomes 2 2 becomes 3 9 becomes 0 0 becomes 1 For the rightmost digit an E option is included to switch to exponential notation To change the sign of a value 1 Select to move to the space that is immediately left of the leftmost digit 2 Use Scroll to specify for a negative value or blank for a positive value In decimal notation you can change the position of the decimal poin...

Page 140: ...n any unsaved edits are lost The system reverts to the previously saved value Note While in exponential notation the positions of the decimal point and exponent are fixed Figure C 3 Numeric values in exponential notation To change from exponential to decimal notation 1 Select until the E is flashing 2 Scroll to d 3 Select The display changes to remove the exponent To exit the menu If the value has...

Page 141: ...s used for display variables Code or abbreviation Definition Comment or reference AVE_D Average density AVE_T Average temperature BRD T Board temperature DGAIN Drive gain GSV F Gas standard volume flow GSV I Gas standard volume flow inventory LPO_A Left pickoff amplitude LVOLI Volume inventory LZERO Live zero flow MASSI Mass inventory MTR T Case temperature PWRIN Input voltage Refers to power inpu...

Page 142: ...O Inputs outputs LANG Display language MAO mA output MASS Mass flow MFLOW Mass flow MSMT Measurement MTR F Meter factor OFF LINE MAINT Off line maintenance menu OFFLN Display off line menu PRESS Pressure r Revision SENSR Sensor SIM Simulation SPECL Special SrC Source Variable assignment for outputs TEMPR Temperature VER Version VFLOW Volume flow VOL Volume or volume flow XMTR Transmitter Table C 2...

Page 143: ...otion com Menu flowcharts for using ProLink II with the Model 2200S transmitter are provided in Figures 2 2 through 2 4 D 2 Requirements ProLink II v2 8 or later is required In addition you must have either the ProLink II installation kit appropriate to your PC and connection type or the equivalent equipment See the ProLink II manual or quick reference guide for details D 3 Configuration upload do...

Page 144: ... transmitter housing cover see Section C 3 b Connect the HART signal converter leads to the HART clips on the face of the transmitter see Figure D 2 The HART Bell 202 connection is polarity insensitive You can connect either lead to either clip Note The HART clips on the face of the transmitter are connected to the transmitter s mA HART terminals You may connect directly to the mA HART terminals t...

Page 145: ...l b If you are using a USB signal converter enable Converter Toggles RTS c Set the Address or Tag value to the HART address or software tag configured for the transmitter The default HART address is 0 See Section 3 3 for information on the HART address and software tag d Set the Serial Port value to the PC COM port assigned to this connection e Set Master as appropriate If another host such as a D...

Page 146: ...ist of all devices on the network b Check all the wiring between the PC and the transmitter c Increase or decrease resistance Note For more troubleshooting information see Section 10 14 3 D 5 ProLink II language ProLink II can be configured for the following languages English French Spanish German Note Other languages may be available depending on the version of ProLink II To configure the ProLink...

Page 147: ...miliar with the Communicator and can perform the following tasks Turn on the Communicator Navigate the Communicator menus Establish communication with HART compatible devices Transmit and receive configuration information between the Communicator and HART compatible devices Use the alpha keys to type information If you are unable to perform the tasks listed above consult the Communicator manual be...

Page 148: ...erminals to report a process variable and also for HART communications see the transmitter installation manual for wiring diagrams E 3 1 Connecting to HART clips To connect the Communicator to the transmitter s HART clips 1 Remove the user interface cover see Section C 3 2 Connect the Communicator leads to the HART clips on the face of the transmitter The connection is polarity insensitive See Fig...

Page 149: ...ce to the connection if necessary Figure E 2 Connecting to a multidrop network E 4 Using the Communicator with the Model 2200S All Communicator procedures assume that you are starting at the on line menu Online appears on the top line of the Communicator main menu when the Communicator is at the on line menu Menu flowcharts for using the Communicator with the Model 2200S transmitter are provided i...

Page 150: ...142 Micro Motion Model 2200S Transmitters ...

Page 151: ...tion 2 139 menu flowcharts 13 process variables viewing values 87 requirements 113 safety messages 141 status alarms 90 totalizers and inventories resetting 93 starting and stopping 93 viewing values 91 Configuration backing up and restoring 82 burst mode 69 characterizing 31 damping added damping 64 density 45 flow 49 temperature 47 default values 123 density cutoff 44 damping 45 measurement 44 m...

Page 152: ...wnload 135 Connecting to the transmitter with ProLink II 135 with the Communicator 140 Customer service 3 104 Cutoff density 44 GSV flow 42 mass flow 38 volume flow 42 D Damping 49 density 45 flow 36 See also Added damping temperature 47 Default values 123 Density cutoff 44 damping 45 factor 47 measurement unit 44 slug flow 45 Density calibration 98 Device parameters 59 Digital communications para...

Page 153: ...st mode See Burst mode 69 HART communication loop troubleshooting 113 HART output troubleshooting 105 HART tag See Software tag HART variables 68 I I O troubleshooting 106 Inventories definition 90 resetting 92 stopping and starting 92 viewing values 90 L Language used by ProLink II 138 used on display 51 Last measured value timeout See LMV Timeout LMV timeout 58 Loop current mode 67 Loop test 75 ...

Page 154: ...iguration upload and download 135 connecting to transmitter 135 language 138 menu flowcharts 11 process variables viewing values 87 requirements 135 saving configuration files 135 status alarms 89 totalizers and inventories resetting 93 starting and stopping 93 viewing values 91 version 2 114 PV See Primary variable Q Quaternary variable 68 QV See Quaternary variable R Range See mA output scale Re...

Page 155: ...wiring 113 process variables 110 receiving device 114 sensor circuitry 117 sensor simulation 82 slug flow 114 status alarms 107 test points 116 transmitter does not communicate 104 transmitter does not operate 104 wiring problems 113 zero failure 104 TV See Tertiary variable Two phase flow See Slug flow U Unit density 44 GSV flow 39 mass flow 37 See also Special unit temperature measurement 46 vol...

Page 156: ...148 Micro Motion Model 2200S Transmitters ...

Page 157: ......

Page 158: ...ku Tokyo 140 0002 Japan T 81 3 5769 6803 F 81 3 5769 6844 Micro Motion Asia Emerson Process Management 1 Pandan Crescent Singapore 128461 Republic of Singapore T 65 6777 8211 F 65 6770 8003 Micro Motion United Kingdom Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U K T 44 0870 240 1978 F 44 0800 966 181 2008 Micro Motion Inc All rights reserved P N M...

Reviews: