Configuration and Use Manual
61
Op
eratio
n
App
e
ndi
ces
Mai
n
tenan
c
e and
T
roub
le
sh
oo
tin
g
Com
m
is
si
on
in
g
Chapter 6
Integrating the Meter with the Control System
6.1
Overview
This chapter discusses the following topics and tasks:
•
Configuring the mA output – see Section 6.2
•
Configuring digital communications – see Section 6.3
Before beginning configuration, make an administrative connection to the transmitter and ensure that
you are complying with all applicable safety requirements.
6.2
Configuring the mA output
The mA output is used to report a process variable. The mA output parameters control how the
process variable is reported.
Table 6-1 lists the parameters that must be set for the mA output, and shows the names used for each
parameter by the display, the Communicator, and ProLink II.
Note: If you use the display, you can configure only the process variable, LRV, and URV.
For details on mA output parameters, see Sections 6.2.1 through 6.2.4.
Table 6-1
mA output configuration parameters
Parameter
Parameter name
Display
Communicator
ProLink II
Process variable
SRC
PV
Primary variable
Range
12 mA
PV LRV
Lower range value
20 mA
PV URV
Upper range value
AO cutoff
Not accessible
PV AO cutoff
AO cutoff
Added damping
Not accessible
PV AO added damp
AO added damp
Fault action
Not accessible
AO1 fault indicator
AO fault action
Fault value
Not accessible
mA1 fault value
AO fault level
Summary of Contents for 2200S
Page 8: ...vi Micro Motion Model 2200S Transmitters ...
Page 12: ...4 Micro Motion Model 2200S Transmitters ...
Page 32: ...24 Micro Motion Model 2200S Transmitters ...
Page 38: ...30 Micro Motion Model 2200S Transmitters ...
Page 68: ...60 Micro Motion Model 2200S Transmitters ...
Page 92: ...84 Micro Motion Model 2200S Transmitters ...
Page 102: ...94 Micro Motion Model 2200S Transmitters ...
Page 110: ...102 Micro Motion Model 2200S Transmitters ...
Page 130: ...122 Micro Motion Model 2200S Transmitters ...
Page 134: ...126 Micro Motion Model 2200S Transmitters ...
Page 150: ...142 Micro Motion Model 2200S Transmitters ...
Page 156: ...148 Micro Motion Model 2200S Transmitters ...
Page 157: ......