9
Wiring
continued
Wirin
g
Sta
rt
up
T
roub
lesh
ootin
g
Bef
o
re
Y
ou Be
gin
Mou
n
ting
2.3
Sensor wiring
The instructions in this section explain how to connect a fully prepared
Micro Motion flowmeter cable to the RFT9709 and a sensor. The sensor
can be a Model D, DL, DT, ELITE
®
, or BASIS
®
sensor.
• The procedure for preparing Micro Motion flowmeter cable and cable
glands is described in the instructions that are shipped with the cable.
• Install cable and wiring to meet local code requirements.
• Use Micro Motion color-coded cable.
• Total length of cable from the sensor to the RFT9709 must not exceed
1000 feet (300 meters).
WARNING
Failure to comply with requirements for intrinsic
safety in a hazardous area could result in an
explosion.
Sensor wiring is intrinsically safe.
• Keep intrinsically safe sensor wiring separated from
power-supply wiring and output wiring.
• For intrinsically safe sensor installations, use this
document with Micro Motion UL installation instructions.
CAUTION
Improper installation of cable or conduit could cause
inaccurate measurements or flowmeter failure.
Keep sensor cable away from devices such as
transformers, motors, and power lines, which produce
large magnetic fields.
09wire.fm Page 9 Monday, March 1, 1999 4:31 PM
Summary of Contents for Fisher-Rosemount RFT9709
Page 1: ...Model RFT9709 Transmitter Instruction Manual March 1999 ...
Page 2: ......
Page 4: ......
Page 8: ...iv RFT9709 Transmitter Instruction Manual ...
Page 34: ...26 RFT9709 Transmitter Instruction Manual ...
Page 52: ...44 RFT9709 Transmitter Instruction Manual ...
Page 60: ...52 RFT9709 Transmitter Instruction Manual ...
Page 62: ...54 RFT9709 Transmitter Instruction Manual ...
Page 72: ...64 RFT9709 Transmitter Instruction Manual ...
Page 73: ......