5.  FAULT TROUBLE SHOOTING 

 

1. 

If the UPS is not operational after Eskom has come back on after load shedding then it could 
be one of three scenario’s: 

a.  The Eskom power has been off an extended period and the batteries have gone flat due to 

the fact that even in standby mode the UPS will still be drawing a charge from the batteries. 

b.  The UPS is in need of a software upgrade to correct the fault 
c.  There is a fault with the batteries. 

 

If the system is non-operational (no lights are on) once the custodian enters the cubicle the 
following steps need to be completed: 

 
1) 

Ensure the breaker on the side of the unit is turned down. 

2) 

Check that all the LCD display lights are off. 

3) 

Ensure that the UPS is plugged into Eskom and the Eskom power to the UPS is off. 

4) 

Turn the ATM off if it is still on.  

5) 

Plug the ATM and V-Sat into Eskom and power up to ensure no fault with the ATM. 

6) 

Power down the ATM if there is no fault. 

7) 

Re-connect the ATM and V-Sat into the adaptor supplied which is connected to the UPS. 

8) 

Flip the breaker on the side of the UPS into the up position. 

9) 

The unit will turn on using the batteries. 

10)  The UPS LCD display should state “Please wait….” 
11)  The LCD display then states “UPS Turned Off …. Calibrating” 
12)  The LCD display then states  “UPS Turned Off” 
13)  Then depress the center button (green) and left button (yellow) for 3 seconds. 
14)  The LCD Display will then state “UPS Turned On” 
15)  Once this phase is completed the UPS should be in operational mode. 
16)  Power up the ATM without turning on Eskom. 
17)  Once the ATM is on turn the Eskom plug that is connected to the UPS on.  
18)  The yellow light should after 3 seconds go out and the green light should come on. This 

indicates that the UPS is running on mains power.  

 

After 5 minutes when both the ATM and the UPS are operational follow this procedure: 

 

1) 

Switch the Eskom plug that is connected to the UPS off. 

2) 

After 3 seconds the green light will go out and the yellow light will come on. This implicates 
that the UPS is running on batteries. 

3) 

Ensure that the power supply to the ATM has not been disengaged and that it is operating 
normally. 

4) 

Wait for 2 minutes then switch the Eskom plug to the UPS back on. 

5) 

After 3 – 5 seconds the yellow light will go off and the green light will come back on. 

The unit has been tested if only briefly that it will switch from Eskom to the batteries should a 
power failure occur. The unit should now be fully operational. 
 
 
 
 
 
 
 
 

Summary of Contents for 1kW24V

Page 1: ...0 1Kw24V UPS Manual...

Page 2: ...1 Contents 1 INTRODUCTION 2 2 SAFETY INSTRUCTION 2 3 SYSTEM DESCRIPTION 3 4 UPS OPERATION 4 5 UPS PROGRAMMING 9 5 FAULT TROUBLE SHOOTING 18...

Page 3: ...self diagnostic function 4 High Power 3 stage Charger 5 High efficiency design to save electricity 6 Low heat dissipation in long time operation 7 Design to operate under harsh environment 1 3 Importa...

Page 4: ...3 2 3 DOWN Key Use to move the display down 3 2 4 ENTER Key It is pressed with the UP Key to turn on the UPS Push the ENTER button to confirm or store DATA 3 2 5 Push the UP and DOWN keys together to...

Page 5: ...ay then changes to The display then changes to UPS TURNED OFF CALIBRATING MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error MICROCARE 1 KW OUTPUT LOW MICROCARE ON OFF ENTER Menu Down Menu Up...

Page 6: ...l change to indicate the amount of LOAD as a of the UPS unit being used in KW When the Up key and the Down Key are pressed simultaneously for 3 seconds the UPS will be turned Off LCD DISPLAY MENU With...

Page 7: ...UPS is drawing from the battery If the battery Amps changes to CHR AMPS This shows the Charge Amps that are being put back into the battery bank from the charging source MICROCARE 1 KW OUTPUT 20 MICR...

Page 8: ...draw from the grid power supply This shows the internal temperature of the UPS TEMPERATURE COOL MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error UPS VOLTS 222 UPS AMPS 7 0 MICROCARE ON OFF E...

Page 9: ...umber of the Inverter The Serial number of the inverter needs to be noted and supplied when requesting any fault support information SERIAL NUMBER MCxx007 MICROCARE ON OFF ENTER Menu Down Menu Up OK I...

Page 10: ...Push ENTER if you want to change the set up menu By pushing ENTER button you can change whether the inverter runs in NORMAL SENSE mode or SOLAR CONTROL mode NORMAL SENSE is to be selected whenever usi...

Page 11: ...nstantly with mains fail prediction 8mS SOFTSTART Default 8 milli second transfer time and will ramp the RMS voltage up in less than 1 second with mains fail prediction GEN SOFTSTART 8 milli second tr...

Page 12: ...ter a medium delay time period HIGH 3x RESET High sensitivity to short circuits will trip the inverter after a short delay time period with soft start to prevent in rush current MED 3x RESET Medium se...

Page 13: ...will then change to The settings available are as follows NO DELAY As soon as Grid power is available the Inverter will synchronise and switch from battery to Grid DELAY 30Sec 30 seconds after Grid po...

Page 14: ...display will show EXIT DO NOT SAVE SET UP MENU MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error RESTORE FACTORY SET UP MENU MICROCARE ON OFF ENTER Menu Down Menu Up OK Inverter Error EXIT AN...

Page 15: ...how If no entry is made for 1 minute the display will return to the main menu Use the UP DOWN button to select BATTERY menu Push ENTER to access the Battery Setup Menu SAVING DATA TO INTERNAL MENU MIC...

Page 16: ...5 of charge rate as per the list supplied below INVERTER CHARGE AMPS 1Kw24V 30A In regards to the battery charge level The Level selected will allow the battery charge to the batteries 25 OF RATED CHR...

Page 17: ...UP button The menu will then change to This allows the user to select the TIME that the BOOST VOLTAGE will be held at before changing to FLOAT By pushing ENTER you can select 1 2 or 3 hours BATTERY B...

Page 18: ...s If the charger is in FLOAT but you require it to go back into BOOST then the next menu will allow this Pushing the ENTER button allows the charge to be changed from AUTO to BOOST or FLOAT Push the U...

Page 19: ...tteries 10 The UPS LCD display should state Please wait 11 The LCD display then states UPS Turned Off Calibrating 12 The LCD display then states UPS Turned Off 13 Then depress the center button green...

Page 20: ...he re connection procedure listed above d If the ATM has any liquid damage or lightning strikes please log a fault report e Should the UPS still remain non operational once the power has been re conne...

Page 21: ...erminals When considering any electronic breakage except due to lightning reverse polarity over voltage etc the state of the internal control circuitry determines the warranty This warranty will not a...

Page 22: ...items purchased from J J Electronics and we require the following information 1 Details of the item s you would like to return 2 Our invoice number 3 The reason for the return 4 J J Electronics must...

Reviews: