MC2-30V
Doc. N°
MO-0499-ING
Copyright 2019
Date
17.03.2022
Rev.
2
Pag. 44
of
63
17.22.3 – Available on software
Int
er
na
l D
is
k
DskClean
Disk near Full clean operation is required
DskFull
Disk Full Write should be lock
DskWR
Disk write in progress
DskFRMT
Disk Format in progress
DskCHK
Check disk in progress
1U>
1U>
Alarm
First overvoltage element
t1U>
Trip
2U>
2U>
Start
Second overvoltage element
t2U>
Trip
1U<
1U<
Start
First undervoltage element
t1U<
Trip
2U<
2U<
Start
Second undervoltage element
t2U<
Trip
1f>
1f>
Start
First overfrequency element
t1f>
Trip
2f>
2f>
Start
Second overfrequency element
t2f>
Trip
1f<
1f<
Start
First underfrequency element
t1f<
Trip
2f<
2f<
Start
Second underfrequency element
t2f<
Trip
1Uo>
1Uo>
Start
t1Uo>
Trip
2Uo>
2Uo>
Start
t2Uo>
Trip
U1<
U1<
Start
tU1<
Trip
U2>
U2>
Start
tU2>
Trip
1df/dt
1df/dt
Start
2df/dt
2df/dt
Start
TCS
tTCS
Start
trip coil supervision
IRF
IRF
Start
Internal Relay Failure
tIRF
Trip
Characte
ristic
Charat 1
Switch to SetUp Group 1
Charat 2
Switch to SetUp Group 2
Charat 3
Switch to SetUp Group 3
Charat 4
Switch to SetUp Group 4
C/B
manOpCmd
Manual Open Command
CL-Cmd
Close Command
C/Bfail
Circuit Breaker failure
L/Rdisc
Local/Remote signal Discrepancy
Gen.Start
Start Generic
Gen.Trip
Trip Generic
UserTriggerOscillo
User Variable for Oscillographic Recording
UserVar<0>
User Variable
to
UserVar<24>
Vcc
Reserved
Gnd
Reserved
ResLog
Reset signal logic
P1
Push-button
to
P6
0.D1
Digital Input “0.D1”
activated
Digital Inputs
0.D1Not
Digital Input “0.D1”
deactivated
to
0.D8
Digital Input “0.D8”
activated
0.D8Not
Digital Input “0.D8”
deactivated