MC2-30V
Doc. N°
MO-0499-ING
Copyright 2019
Date
17.03.2022
Rev.
2
Pag. 21
of
63
12. Trip Recording
Display of the function which caused the tripping of the relay plus values of the measurement at the moment of
tripping. The last 30 events are recorded.
The memory buffer is refreshed at each new relay tripping (FIFO logic).
Display
→
Reading of recorded Trips.
Erase
→
Clear all Trips recorded.
1
•
Press “
Menu
” for access to the main menu with icons.
2
•
Select “
TripRec.
” icon with pushbutton
“
Increase
” or “
Decrease
”.
•
Press “
Select
” for access.
3
•
Select “
Display
” with pushbutton
“
Increase
” or “
Decrease
”.
•
Press “
Select
” for access.
•
For “
Erase
” go to “8”
4
•
If no trip is recorded the display shows “
No Trips
”.
5
•
If any trip was recorded, select “
View
” to display the chronological list of the
records.
•
By the keys
“
Increase
” or “
Decrease
” select the date of the record to be
checked.
6
•
Will be shown:
“
Descr
” the function that caused the event (Example: t1I> = Rise)
“
Edge
” if the function was tripped (Rise) or reset (Fall)
“
Date
”, date of trip, year/month/day, hour:minutes:seconds:milliseconds
•
Press “
Value
”, for reading the value of input quantities on tripping.