17.23 - Function:
CB Mngn
(Control C/B)
This menu allows to configurate the command for C/B operation.
Options
→
L/R
Ignored
[Ignored / Active]
→
Key
Enable
[Disable / Enable]
→
Key0
None
[None / P1 / P2 / P3 / P4 / P5 / P6]
→
KeyC
None
[None / P1 / P2 / P3 / P4 / P5 / P6]
Timers
→
tL/R
0.05
s
(0.05
÷
1)
step
0.05
→
tC/Bs
0.5
s
(0.05
÷
1)
step
0.05
17.23.1 - Description of variables
L/R
: Selection of Local/Remote C/B operation mode Ignored or Active
Key
:
Disable
= The pushbuttons on Front Panel are disabled;
Enable
= The pushbuttons on Front Panel are Enable
Key0
: Configure a Key as C/B Open
KeyC
: Configure a Key as C/B Close
tL/R
: Admissible time before detection of the Local/Remote discrepancy alarm.
tC/Bs
: Maximum admissible delay for detection of status signal after C/B operation.
17.23.2 – Push-Buttons (Programmable only via software)
It is possible to program up to six buttons on front of the relay, assigning any action / function.
Example: “
” to “
” and “
” to “
”.
17.23.2.1 – “DI Configurations” (Digital Inputs)
Select “
DI configuration
”:
Assign to:
Type
Functions
Main C/B CloseSts
0.D1
digital input
Local State
0.D3
digital input
Remote State
0.D4
digital input