background image

 

 

MC20-CEI 

Doc. N°

 MO-0431-ING 

 

Microelettrica Scientifica S.p.A. - Copyright 2009    

FW  1080.36.03.X 

Date  18.11.2011 

Rev. 

 

Pag.  32 

of  35 

 
 

 
14. Password 

 

This password is requested anytime the user wants to write in the “

Settings

” menu a command of the “

Commands

” 

menu. 
 
The default password is “ 

1111

 “ 

 
When password is required, proceed as follows 
 
The Display shows the message “ 

Password ????

 “ 

 

 

to select 1

st

 digit (1-9) 

  to validate 

 

to select 2

nd

 digit (1-9) 

  to validate 

 

to select 3

rd

 digit (1-9) 

  to validate 

 

to select 4

th

 digit (1-9) 

  to complete procedure. 

 

The “ 

password

 “ is required any time you attempt to modify one of the programmable variables at the first entrance 

in the “

Settings

” and/or “

Commands

” menus. 

The  “  password  “remains  valid  for  2  minutes  from  the  last  operation  of  the  programming  buttons  or  until  the 

 

button is pressed to return to the default display (RT Meas). 
Once the Password has been entered, a “ 

#

 “ appears before the variable that can be modified. 

 

14.1 - MS-Com Password 

 

This  password  is  requested  anytime  the  user  wants  to  send  to  the  relay  a  setting  parameters 
modification or to issue a command through the relay itself using the managing software MSCom. 
The  user  can  decide  whether  inserting  his  own  password  (see  MS-Com  Operational  Manual)  or 
keeping the password disabled just clicking on the OK button when the password is requested. 

 
15. Maintenance 

 

No maintenance is required. In case of malfunctioning please contact  Microelettrica Scientifica Service 
or the local Authorised Dealer mentioning the relay's Serial No reported in the label on relays enclosure. 
 

 

16. Power Frequency Insulation Test 

 
Every relay individually undergoes a factory insulation test according to IEC60255-5 standard at  
2 kV, 50 Hz 1min. Insulation test should not be repeated as it unusefully stresses the dielectrics.  
When doing the insulation test, the terminals relevant to serial output, digital inputs and RTD input must 
always be short circuited to ground.  When relays are mounted in switchboards or relay boards that have 
to  undergo  the  insulation  tests, the relay  should  be  isolated. This  is  extremely  important  as  discharges 
eventually  tacking  place  in  other  parts  or  components  of  the  board  can  severely  damage  the  relays  or 
cause damages not immediately evident to the electronic components. 
 

Summary of Contents for MC20-CEI

Page 1: ...Doc N MO 0431 ING Microelettrica Scientifica S p A Copyright 2009 FW 1080 36 03 X Date 18 11 2011 Rev 3 OVERCURRENT AND DIRECTIONAL EARTH FAULT PROTECTION ACCORDING TO CEI 0 16 TYPE MC20 CEI OPERATIO...

Page 2: ...___________________________________________________ 19 7 Self diagnostic _________________________________________________________________________________________________ 19 8 Relay Management________...

Page 3: ...1 5 Outputs Loading must be compatible with their declared performance 1 6 Protection Earthing When earthing is required carefully check its effectiveness 1 7 Setting and Calibration Carefully check t...

Page 4: ...e to the instruction manual of the Manufacturer maintenance must be carried out by specially trained people and in strict conformity with the safety regulations 1 11 Waste Disposal of Electrical Elect...

Page 5: ...ed Digital Inputs RS485 communication port independent from the RS232 port on front panel Totally draw out execution with automatic C T shorting device Input currents are supplied to 3 current transfo...

Page 6: ...put the value I1 of the primary current of the phase C Ts Only phase A and C currents are measured whereas the current of the phase B is computed as vector summation of the currents of the other two p...

Page 7: ...rent from I1 2 2 2 4 Algorithm of the time current curves The Time Current Curves are generally calculated with the following equation 1 r S a T T K B 1 Is I A t I where t I Actual trip time delay whe...

Page 8: ...MC20 CEI Doc N MO 0431 ING Microelettrica Scientifica S p A Copyright 2009 FW 1080 36 03 X Date 18 11 2011 Rev 3 Pag 8 of 35 2 2 3 Time Current Curves IEC TU1029 Rev 0...

Page 9: ...MC20 CEI Doc N MO 0431 ING Microelettrica Scientifica S p A Copyright 2009 FW 1080 36 03 X Date 18 11 2011 Rev 3 Pag 9 of 35 2 2 4 Time Current Curves IEEE TU1028 Rev 0...

Page 10: ...Definite Time A IEC A Inverse B IEC B Very Inverse C IEC C Extremely Inverse MI IEEE Moderate Inverse Curve VI IEEE Very Inverse Curve I IEEE Inverse Curve EI IEEE Extremely Inverse Curve SI IEEE Sho...

Page 11: ...ult protection level Stato Status Abilit Disabl Disable Abilit Enable Opzioni Options BI Disab Disabl Disable Abilit Enable Livelli Trip Level Io 0 50 Ion 0 01 4 00 step 0 01 Ion Tempi Timer tIo 0 50...

Page 12: ...BI Operation controlled by Blocking Digital Input Io 1 Trip level Uo 1 Trip level aA 1 First angle trip sector aB 1 Second angle trip sector t67 1 Trip time delay 2 2 5 8 67S2 Second Directional Earth...

Page 13: ...RF signal led without tripping the output relays OpI NoTRIP 2 2 5 10 AnIn Circuit Breaker Failure F51BF Stato Status Abilit Disabl Disable Abilit Enable Opzioni Options TrR Rele1 Relay1 Relay2 Relay3...

Page 14: ...me delay Operation The relay includes a complete Circuit Breaker Trip Circuit Supervision unit that is associated to the Contact 13 12 The supervision works when the C B is closed and recognizes the T...

Page 15: ...on of Keyboard buttons Off after 10sec of inactivity 2 2 5 13 Comm Communication Parameters Stato Status Non Disp Non Disp No Parameters Opzioni Options LBd 9600 9600 19200 38400 57600 RBd 9600 9600 1...

Page 16: ...showed or exported the export format is compliant with IEC 0 16 through the MSCom2 software Available Elements Logic Events Starts Trips Changing Change the setting parameters Power Supply on Power on...

Page 17: ...port Select export mode YES the events are sorted from newest to oldest NO events will be sorted from oldest to newest Select export YES the information will be exported to a test file txt NO will be...

Page 18: ...e explained in case of Breaker Failure the blocking output is released and the back up protection enabled 4 2 Blocking Input The blocking action of any protection functions can be controlled by activa...

Page 19: ...52c Input Closed C B closed Input Open C B open 7 Self diagnostic The relay incorporates a sophisticated self diagnostic feature that continuously checks the following elements A D conversion Checksum...

Page 20: ...ment The relay can be totally managed locally either by the RS232 communication port or by the 4 key buttons and the LCD display or remotely via the communication bus RS485 connected to the rear termi...

Page 21: ...rts to operate Illuminated when any function is tripped reset takes places by pressing the reset button d Yellow LED PWR I R F Illuminated during normal operation when Power Supply is ON Flashing when...

Page 22: ...RS485 and the Communication Protocol is MODBUS RTU IEC60870 5 103 The configuration of transmission parameters is selectable Baud Rate 9600 19200 bps 9600 19200 bps 9600 19200 bps Start bit 1 1 1 Dat...

Page 23: ...of 35 11 2 Communication Port on Front Face Panel This port is used for communication through the Front Face Panel between a local Lap top PC The physical link is RS232 by the standard female 9 pin D...

Page 24: ...of the 3 phase currents of rated current IA 0 65535 A RMS value of Phase A current Primary Amps IB 0 65535 A RMS value of Phase B current Primary Amps IC 0 65535 A RMS value of Phase C current Primar...

Page 25: ...e used I First overcurrent element Short Circuit I Second overcurrent element Short Circuit I Third overcurrent element Short Circuit Io First earth fault element Io Second earth fault element 67S1 Fi...

Page 26: ...XX hh mm to set hour XX mm to set minutes To validate Set Done Exit 12 5 3 Val Nom Rated Input Values Val Nom Rated Input Values 1 st Variable to scroll variables to modify selected variable Password...

Page 27: ...bilit Enable of the protection function Abilit Disabil TCC D Time Current Curves D A B C I VI EI MI SI Opzioni BI Disabil Operation controlled by Blocking Digital Input Abilit Disabil Livelli I 0 50 I...

Page 28: ...ivelli aB 2 280 Second angle trip sector 0 360 1 67S2 Tempi t67 2 0 70 s Trip time delay 0 05 1 00 0 01 Stato Abilit Enable of the protection function Abilit Disabil Opzioni Opz NoScatto Operation of...

Page 29: ...TCS tTCS HwRec Relay1 R1 ModoOp N D N D Normally Deenergized N E Normally Energized N D N E Link tTCS AnIn BF Association of functions to output relay R2 I tI I tI I tI Io tIo Io tIo 67S1 t67S1 67S2...

Page 30: ...memory of trip counters resDLog Erase memory of Event recording UltimiSc and Data logger LedTest Test signalization leds Riarmo Reset after trip ApInt Manual Open Close Breaker ChInt Manual Close Clos...

Page 31: ...MC20 CEI Doc N MO 0431 ING Microelettrica Scientifica S p A Copyright 2009 FW 1080 36 03 X Date 18 11 2011 Rev 3 Pag 31 of 35 13 Keyboard Operational Diagram...

Page 32: ...ng parameters modification or to issue a command through the relay itself using the managing software MSCom The user can decide whether inserting his own password see MS Com Operational Manual or keep...

Page 33: ...CEI Doc N MO 0431 ING Microelettrica Scientifica S p A Copyright 2009 FW 1080 36 03 X Date 18 11 2011 Rev 3 Pag 33 of 35 17 Wiring Diagram 18 Overall Dimensions mm Protection Degree IP44 on request I...

Page 34: ...ws in the horizontal position of the screws driver mark Draw out the PCB by pulling on the handle 19 2 Plug In Rotate clockwise the screws in the horizontal position of the screws driver mark Slide in...

Page 35: ...t transient burst IEC61000 4 4 level 3 2kV 5kHz HF disturbance test with damped oscillatory wave 1MHz burst test IEC60255 22 1 class 3 400pps 2 5kV m c 1kV d m Oscillatory waves Ring waves IEC61000 4...

Reviews: