DTMR3-TX
Doc. N°
MO-0377-ING
Copyright 2010
Data
01.04.2009
Rev.
0
Pag.
11
of
87
9.
Max.Val.
(Inrush maximum measure values)
Maximum demand values recorded starting from 100ms after closing of main Circuit Breaker
(updated any time the breaker closes).
1
Press “
Menu
” for access to the main menu with icons.
2
Select “
MaxVal
” icon with pushbutton
“
Increase
” or “
Decrease
”.
Press “
Select
” for access.
3
Scroll the menu “
MaxVal
”
with pushbutton
“
Increase
” or “
Decrease
” to display
the measure
Press “
Exit
” to go back to the main menu.
dA
(0
99.99)
In
RMS phase A differential value
dB
(0
99.99)
In
RMS phase B differential value
dC
(0
99.99)
In
RMS phase C differential value
Io2
(0
9999)
A
Earth fault current side 2
1A
(0
9999)
A
RMS value of phase A side 1
1B
(0
9999)
A
RMS value of phase B side 1
1C
(0
9999)
A
RMS value of phase C side 1
2A
(0
9999)
A
RMS value of phase A side 2
2B
(0
9999)
A
RMS value of phase B side 2
2C
(0
9999)
A
RMS value of phase C side 2
d2A
(0
999)
%
2
nd
harmonic phase A
d5A
(0
999)
%
5
th
harmonic phase A
d2B
(0
999)
%
2
nd
harmonic phase B
d5B
(0
999)
%
5
th
harmonic phase B
d2C
(0
999)
%
2
nd
harmonic phase C
d5C
(0
999)
%
5
th
harmonic phase C
IR
(0
99.99)
In
Selected bias through current
Wir
(100
0)
%W
Amount still remaining of permissible interruption energy before Circuit
Breaker maintenance is requested.