14.1 Modifying the setting of variables
To modify any variable settings by the keyboard proceed as follows:
(example: change setting of element “
1I>
”, from “
Is
4.000
In
” to “
Is
3.500
In
”)
1
Press “
Menu
” for
access to the main
menu with icons.
7
The value
appears as bold
figure.
2
Select icon “
Setting
”
by pushbutton
“
Increase
” or
“
Decrease
”.
8
Set new value by
“
Increase
” or
“
Decrease
” buttons
Press “
Select
”.
Press “
Write
”.
3
Select “
Group
” by
pushbuttons
“
Increase
” or
“
Decrease
”.
9
If the parameters
change is
completed, press
“
Exit
”.
Press “
Select
”.
4
Select by
pushbuttons
“
Increase
” or
“
Decrease
” the
parameter “
1d>
”.
10
“
Yes
” to confirm all
changes.
Press “
Select
”.
“
No
” voids all the
changes.
5
Select by buttons
“
Increase
” or
“
Decrease
” the menu
“
Oper.Levels
”.
11
The relay returns to
point “
4
”.
Press “
Select
”.
6
The arrow aside “
Is
”
shows the parameter
selected for changing
Press “
Modify
”.
If Password is
request, see §
Password