DTMR3-TX
Doc. N°
MO-0377-ING
Copyright 2010
Data
01.04.2009
Rev.
0
Pag.
42
of
87
14.16 - Function:
CB Mngn
(Control C/B)
This menu allows to configurate the command for C/B operation.
Options
L/R
Ignored
[Ignored
– Active]
Key
Enable
[Disable
– Enable]
Timers
tL/R
0.05
s
(0.05
1.00)
step
0.05
s
tC/Bs
0.50
s
(0.05
1.00)
step
0.05
s
14.16.1 - Description of variables
L/R
: Selection of Local/Remote C/B operation mode Ignored or Active
Key
:
Disable
=
The pushbuttons on Front Panel are disabled;
the operation of the C/B can be controlled by;
1 - serial bus commands
2 -
commands available in the menu “
Cmd
”
(Password protected).
3 - Digital Inputs.
Enable
=
The C/B can be controlled also by the pushbuttons available
on Relay’s Front Face.
tL/R
: Admissible time before detection of the Local/Remote discrepancy alarm.
tC/Bs
: Maximum admissible delay for detection of status signal after C/B
operation.